Sears GT Series Installation Instructions Manual page 24

Geothermal
Table of Contents

Advertisement

INTELLIGENT
RESET:
If a fault condition
is initiated,
the 5
minute
delay on break
time period is initiated
and the unit will
restart after these delays expire.
During this period the fault LED
will indicate
the cause of the fault. If the fault condition
still exists
or occurs 2 or 4 times (depending
on 2 or 4 setting for Lockout
dip
switch) before 60 minutes,
the unit will go into a hard lockout
and
requires
a manual
lockout
reset.
A single condensate
overflow
fault will cause the unit to go into a
hard lockout
immediately,
and will require a manual lockout
reset.
START
_,,I
NO
RESET
ON R
• LOCKOUT
RESET:
A hard lockout
can be reset by turning
the
unit thermostat
off and then back on when
the "RESET"
dip
switch
is set to "Y" or by shutting
off unit power
at the circuit
breaker
when the "RESET"
dip switch is set to "R".
NOTES:
The blower
motor
will remain
active during
a lockout
condition.
YES
YES
NO
NO
YES
NO
YES
NO
NO
LOCKOUT
CAN
BE SET
TO 4 VIA DIP SWITCH
YES
YES
YES
YES
YES
NO
NO
Fig. 71 - UPM
Sequence
of Operation
(SOO) Flow Chart
24
A14129