Airflow
Selector
The airflow selector (see Fig. 72, items 2 and 3 and Fig. 76) allows
airflow
adjustment
to meet
application
requirements
and to ease
troubleshooting.
NOTE:
Only one switch can be enabled
at a time. Refer to Fig. 76
for each airflow
setting.
• CFM Selector
must remain
with only "A" being
enabled.
• ADJUST
Selector
can be adjusted
to NOM,
(+), (-), or TEST.
NOM, (+) and (-) can be adjusted
as needed by application.
TEST
is used for troubleshooting
to override
unit airflow
to 100%.
ECM CONTROL BOARD
FACTORY DEFAUU SETTINGS
CFM
ADJUST
A
B
C
D
NOM
(+)
(o)
TEST
Fig. 76 - Airflow
Selector
A14125
UNIT
DAMAGE
AND/OR
OPERATION
HAZARD
Failure
to follow
this caution
may
result
in unit damage
and/or improper
equipment
operation.
Do not set the ADJUST
DIP switch to the (-) setting when
electric
heaters
are
installed.
Doing
so may
cause
the
heaters
to
cycle
on
their
thermal
overload
switches,
potentially
shortening
the life of the switches.
UNIT
DAMAGE
AND/OR
OPERATION
HAZARD
Failure
to follow
this caution
may
result
in unit damage
and/or improper
equipment
operation.
Always
disconnect
power
before
changing
DIP
switch
positions
on
the
interface
board
and
reset
the
unit
afterward.
Constant
Airflow
Motor
The Constant
Airflow
Motor
is an Electronic
Conmmtated
Motor
(ECM)
that
provides
a constant
air flow
over
a wide
range
of
external
static pressures
while
optinfizing
the power
consumption
of the motor.
This option
allows
the unit to have different
air flow
settings
depending
on the mode
that
the unit
is operating;
i.e
heating,
cooling,
fan only,
hot gas reheat, etc. Refer
to the ECM
Interface
Board section
in this document
for more information.
Pump
Relay
The factory installed
pump
relay can be used to energize
a supply
pump
or solenoid
valve
when
there
is a call
for compressor
operation.
This
relay
can be used
to switch
either
high
or low
voltage
power.
Comfort
Alert
Diagnostics
Module
(CADM)
The Comfort
Alert Diagnostics
Module
(CADM)
is a breakthrough
innovation
for troubleshooting
heat pump system
failures
(see Fig.
77).
A14127
Fig. 77 - Comfort
Alert
Diagnostics
Module
(CADM)
By monitoring
and analyzing
data from
the compressor
and the
thermostat
demand,
the module
can accurately
detect the cause
of
electrical
and
system
related
failures
without
any
sensors.
A
flashing
LED indicator
conmmnicates
the ALERT
code and guides
the service technician
more quickly
and accurately
to the root cause
of a problem.
IMPORTANT:
This module
does not provide
safety protection!
The Comfort
Alert
Diagnostics
Module
is a monitoring
device
only and cannot
shut down
the compressor
directly.
When
an abnormal
system
condition
occurs,
the CADM
displays
the appropriate
ALERT
and/or
TRIP
LED.
The yellow
ALERT
LED
will flash
a number
of times
consecutively,
pause
and then
repeat
the process.
To identify
a Flash
Code number,
count
the
number
of consecutive
flashes.
Every time the module
powers
up,
the last ALERT
Flash
Code that
occurred
prior
to shut down
is
displayed
for one nfinute.
FACTORY
INSTALLED
FEATURES
A number
of factory
installed
options
are available
on the GT
Series of Heat Pumps.
The following
details the purpose,
function
and components
of each option.
Smart
Start Assist
The Smart Start Assist
Kit is designed
for GT single phase
units.
The kit contains
two main parts;
both
are installed
on top of the
unit's
electrical
box (e-box).
The Smart Start Assist attaches to the
e-box
top via a mounting
plate attached to the Smart Start Assist as
shown
in Fig. 78.
Refer
to the Smart
Start Assist
Installation
Instructions
for further