18

Configuration

This chapter contains information about the following points:
18.1

Menu overview

Configuration
18.2

Physical node address (PNA/RSN)

The physical node address (RSN) of the panel is set in the panel firmware when switching on
the panel for the first time, there are no mechanical rotary switches. It must be identical with
the physical node address configured in the programming software. After a change of the
physical node address (RSN), a reboot of the panel is required.
To change the physical node address enter a number between 1 and 64. Choose OK and
reboot to make the change effective.
18.3

Group setting

Different kind of groups can be created using the FSP-5000-RPS programming software:
Bypass, isolate and walktest groups and input / output groups.
Each group can consist of one or more element(s).
Input groups consist of several detectors and/or logical zones; Output groups consist of
signaling devices and transmission devices. Specify which input group activates which output
group by using the programming software.
You can use the panel controller to carry out the following:
18.3.1

Adding or deleting

In order to add elements to a group or remove elements from it:
1.
2.
3.
4.
5.
Bosch Sicherheitssysteme GmbH
Physical node address (PNA/RSN), page 75
Group setting, page 75
Detector sensitivity, page 77
Operator, page 77
Rename elements, page 78
Network services, page 79
Overview, page 79
-> Set Physical Node
Address (PNA/RSN)
Detector sensitivity
Rename elements
Network services
Adding elements to or removing elements from groups.
Renaming groups.
In the start menu, select Configuration
Set groups
Select the required type of group.
Two different lists are displayed.
Select a list, e.g. By description.
A list of the various input groups is displayed.
Select the list field you require.
The list field is marked.
You can select various options:
Set groups
Operator
Overview