15.3.4 THE BACKFLUSH MODULE

With the backflush module, on the TCU a backflush programme can be set for gas sampling probes
(duration of a backflush pulse, number of backflush pulses, time between backflush pulses, timing of
backflush). The programme switches with time delay two solid-state relays with which in turn solenoid
valves can be switched, which accordingly release purging air to the gas sampling probe.
At start and end of a backflush programme, another solid-state relay is switched one second before start
and after the end of the programme, with which a solenoid valve can be controlled, which releases
control air to shut off and open the sample gas output of the gas sampling probe with pneumatic valve.
In addition, at the start and end of a backflush programme, a changeover relay for status monitoring
(measuring/backflush) is switched. Here at the TCU dead time can be specified to ensure that, on the
"Measure" message, sample gas is currently flowing in the analyser. In addition, a connection is present
for pressure monitoring of the backflush gas. For this purpose, a pressure switch is connected in the
backflush line which closes the contact at upcoming pressure.
Figure 14
Electrical connections backflush module
www.mc-techgroup.com
CSS-VC-1.6 | 1.01.03
31