Airflow Requirements; Servicing Space Requirements; Table 1-27. Airflow Requirements - Western Digital ActiveScale X100 Installation Manual

Hide thumbs Also See for ActiveScale X100:
Table of Contents

Advertisement

ActiveScale™ X100 Installation Guide
Condition (fully configured)
Weight
1.Values are for one additional node. System Expansion Node kits can contain up to three additional nodes.
2.Rackless system height can vary based on the installation. A rackless configuration uses 36U of equipment.
3.The minimum system weight does not include the rack and PDUs

1.3 Airflow requirements

Ensure that both the front and rear of the ActiveScale X100 stay clear of any materials that may block or
disrupt the airflow in any way. Disrupting the airflow can cause the system to overheat, which may affect
performance or cause damage to the system.
The following rack airflow principles should be considered for best results:
• Controlled air conditioners that are functional and can sufficiently maintain specified system
operating temperatures should be located in the facility where the system will be installed.
• The airflow in and out of the equipment must not be restricted.

Table 1-27. Airflow requirements

Condition (fully configured)
Altitude
Relative humidity
Temperature
Temperature de-rating
Temperature gradient
Thermal output

1.4 Servicing space requirements

Space at the front and the rear of the system is required to service system components. The front space
requirement is based on the length of the longest system component, plus the space necessary to fit a
Non-operating
• Minimum system weight
• Full system weight—2227 lbs (1010 kg)
• Delivery weight (system and packaging)—2457 lbs (1114 kg)
Non-operating
-984 ft to 39,3711 ft
(-300 m to 12,000 m)
10% to 95% non-condensing
40°F to 158°F
(-40°C to 70°C)
33.8°F per 984.2 ft above 9842.5 ft
(1°C per 300 m above 3000 m)
86°F (30°C)/hour
N/A
13
Operating
3
—1572 lbs (713 kg)
Operating
-984 ft to 10,000 ft
(-300 m to 3048 m)
8% to 90% non-condensing
50°F to 95°F
(10°C to 35°C)
33.8°F per 984.2 ft above 3116.8 ft
(1°C per 300 m above 950 m)
68°F (20°C)/hour
Partial configuration (one column
populated sleds):
• 8.53/11.26 KBTU/h
Full configuration (seven columns of
populated sleds):
• 21.83/ 25.25 KBTU/h
System Expansion Node kit:
• 0.665 at 0.785 KBTU/hour