APPENDIX
Inverter Communication
Instructions
Inverter parameter block write [IVBWR]
This instruction writes the values set in (s3) to specified inverter parameters at one time when parameter
numbers are specified.
IVBWR
(s1)
(s2)
(s3)
Example program
The following program writes the maximum frequency (Pr.1): 120 Hz, minimum frequency (Pr.2): 5 Hz,
acceleration time (Pr.7): 1 s, and deceleration time (Pr.8): 1 s to the inverter (station number 0).
Initial pulse
SM402
Write command
M10
IVBWR
Instruction execution
completed flag
SM8029
*: Make sure not to use devices being used in other control operations.
(n)
(d)
SET
MOVP
K1
MOVP
K12000
MOVP
K2
MOVP
K500
MOVP
K7
MOVP
K10
MOVP
K8
MOVP
K10
K0
K4
D200
K1
RST
M10
Write command ON
Parameter number
D200
[Pr.1]: Maximum frequency
D201
Maximum frequency: 120 Hz
Parameter number
D202
[Pr.2]: Minimum frequency
D203
Minimum frequency: 5 Hz
Parameter number
D204
[Pr.7]: Acceleration time
D205
Acceleration time: 1 s
Parameter number
D206
[Pr.8]: Deceleration time
D207
Deceleration time: 1 s
M200
Head bit device number for instruction execution status output
Communication channel: K1 to K4
Head for writing parameter table
Number of parameters to be written (decimal)
Inverter station number: 0 to 31
M10
Write command OFF
• D201: [Pr.1] Maximum frequency
• D203: [Pr.2] Minimum frequency
• D205: [Pr.7] Acceleration time
• D207: [Pr.8] Deceleration time
1
2
3
4
5
6
39