5. EXAMPLE PROGRAMS
Operation
1
This program is used for operation stop (X10), forward rotation (X11), and reverse rotation (X12) to control operations of the inverter.
The frequency setting can be changed by changing a value set in D31.
Ladder diagram for the station number 1 (second inverter)
Frequency switching
2
RUN monitor
SM400
3
Operation stop / cancel
Operation stop
command
X10
Forward rotation
command
X11
Reverse rotation
4
command
X12
Forward/reverse rotation switching
Operation
stop
M65
5
Inverter operation control and status check
RUN monitor
SM400
6
28
Operation Check
Switch command
Switch command
(Speed 1)
(Speed 2)
M7
M8
MOVP
Switch command
Switch command
(Speed 1)
(Speed 2)
M7
M8
MOVP
Switch command
Switch command
(Speed 1)
(Speed 2)
M7
M8
MOVP
Operation stop
command
X10
Forward rotation
Reverse rotation
command
command
X11
X12
Reverse rotation
Forward rotation
command
command
X12
X11
MOV
(s1)
(s2)
(s3)
IVMC
K1
H0000
D30
MOV
Inverter running
M300
Forward rotation
M301
Reverse rotation
M302
Alarm occurrence
M315
MOV
Initial value at start-up:
K6000
D31
60 Hz
K4000
D31
Operation speed: 40 Hz
K2000
D31
Operation speed: 20 Hz
Operation stop
SET
M65
(HF b1 and b2: OFF)
Operation stop cancel
RST
M65
(HF9 b1 or b2: ON)
Forward rotation command
M41
(HF9 b1: ON)
Reverse rotation command
M42
(HF9 b2: ON)
K4M40
D30
Operation command write
(d1)
(n)
(d2)
The set frequency (RAM) and operation command
(extended) are written.The inverter status monitor
D40
K1
M400
(extended) and output frequency (rotation speed) are read.
Head bit device number for instruction execution status output
(M400 to M402 are occupied.)
Communication channel: 1
Head device for storing read values (D40 and D41 are occupied.)
Head device for writing data (D30 and D31 are occupied.)
Send/receive data type specification
Inverter station number: 1
Inverter status information read to D40 using the IVMC instruction
D40
K4M300
The information is stored to M300 to M315 using the MOV
instruction.
Y4
Y5
Status details
(as needed)
Y6
Y7
Output frequency (rotation speed) monitor value
D41
D60
Transferred to D60.
When the operation speed is
set to D31, it is stored in
(s3)+1 of the IVMC instruction
as the data to be written to
an inverter.
Information on the forward and reverse
rotation commands is transferred to
D30 using the MOV instruction.
The information in D30 is stored in (s3)
of the IVMC instruction as the data to
be written to an inverter.
Operation
command
Status check
Output
frequency
check