3. PROGRAMMABLE CONTROLLER SETTINGS
Communication
Parameter Settings
Test Programs
5
Select [Inverter Communication] for the communication protocol type to display the following window.
In the "Advanced Settings" field, set parameters for the inverter.
Basic settings
Point
Set the same parameters for the programmable controller and inverters.
Basic settings
Programmable controller
6
After the parameters are set, click the Apply button.
*: In this manual, the parameters set above are written to the programmable controller together with
communication test programs, which will be created in the next section.
Communication
Writing Data to the
Settings
Programmable Controller
Parameter
No.
Pr.118
Pr.119
Pr.120
Parameter item
Description
PU communication speed 19200 bps
PU communication
Data length: 7 bits
stop bit length
Stop bit: 1 bit
PU communication parity check Even
Inverter
1
2
3
Setting
value
4
192
10
2
5
6
19