5.9.8 Commissioning an Exit Button and an Emergency Button

Procedure
Step 1 Check functions of the exit button.
Table 5-33 Function commissioning
Check Method
Attempt to open the door by pressing the
exit button when the aisle door is closed.
Step 2 Check functions of the emergency button.
Table 5-34 Function commissioning
Check Method
Attempt to open the door by
pressing the emergency button
when the aisle door is closed.
----End

5.10 Commissioning CIMs and BIMs

If CIMs and battery interface modules (BIMs) are installed, perform the following steps to
commission.
Procedure
Step 1 Log in to the ECC800 WebUI as an administrator.
Step 2 Choose Monitoring > Power Distribution > CIM > Running Parameters.
Step 3 Set CIM single battery qty., Batt installation time, Battery string capacity, Current
source, and Battery string No. based on
parameters.
Table 5-35 Setting CIM parameters
Parameters
CIM single
battery qty.
Issue 06 (2020-01-02)
Normal Connection
Status
The aisle door is
opened successfully.
Description
Total number of batteries monitored by
the CIM
Copyright © Huawei Technologies Co., Ltd.
Normal Connection Status
The aisle door is opened successfully.
Follow-up Procedure
Press the emergency button
again for restoration.
Table
5-35. Retain default values for other
5 Power-On Commissioning
Remarks
Set this parameter to a
value in the range of 0 to
40 according to the
customer plan.
134