Daikin MicroTech Operation And Maintenance page 66

Unit ventilator controls for applied classroom unit ventilators
Table of Contents

Advertisement

Menu Name
Minimum Password to Read
(Menu Index)
(None, User, Manager, Technician)
DAT
DATSpt:
DATClgSpt:
DATHtgSpt:
AllHtStgsOn:
AllHtStgsOf:
AirTmprgMod:
DAHiLimMode:
CmpAirTmprg:
DATRstClIn:
DATRstHtIn:
RstReHtIn:
DATReHtSpt:
DATDehumSpt:
DATReHtSpt:
NtDATReHtSp:
NtDATClgSpt:
NtDATHtgSpt:
ElectricHeating
ElHtStgOut:
ElectHtAvl:
ElHtCmdStgs:
ElDatLLPIOt:
ElDatLLPIOutStg:
ElDehmPIOut:
ElDehumPIOutStg:
Humidity
EffOutRH:
EffSpaceRH:
OutEnth:
InEnth:
EffHum:
KeyDehumEn:
DehumAvl:
DehumEn:
NetOutRH:
NetSpcRH:
Timers
InStgTmr:
PmpOnTmr:
RoomSensor
RSSysMode:
RSFanSpd:
RemSptAdjType:
Password
PWLevel:
EnterPW:
KeyLUIOnStopPW:
ClearPW:
PWTimer:
Alarms|Active
Active Alarm #1
AlmStat:
KeyRstAls:
TORstAlm:
TechSupport:
AlmCfgStat:
CntrlBoardStat:
MultAlmComp:
Alarms|History
History Alarm #1
TechSupport:
OM 1280-2 • MICROTECH UNIT CONTROLLER
Minimum Password to Write
(None, User, Manager, Technician)
"RO" if Read Only
N
N
N
T
T
M
M
M
M
M
M
M
M
M
N
N
N
T
N
T
T
T
T
T
N
N
M
M
N
N
M
M
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
T
T
T
N
N
Appendix – Local User Interface (LUI)
Help Text
RO
Current DAT setpoint.
RO
DAT Cooling setpoint.
RO
DAT Heating setpoint.
N
Active if all heat stages are on.
N
Active if all heat stages are off.
RO
Tmprng if DAT < HtSpt and not unocc.
RO
Actv if DAT > DAHiLimMode and ht on.
RO
Status of compressor heat air tempering.
RO
Value used in DAT Clg reset control.
RO
Value used in DAT Htg reset control.
RO
DAT reset reheat input.
M
DAT reheat setpt when NONE selected.
RO
DAT Dehumidification setpoint.
RO
DAT reset reheat setpoint.
RO
Network DAT reheat setpoint.
RO
Network DAT cooling setpoint.
RO
Network DAT heating setpoint.
RO
Number of elect ht stages currently on.
RO
Specifies if electric heat is available.
RO
Commanded electric heat stages.
RO
Elect heat DAT LL PI loop output.
RO
Convert ElDatLLPIOut to stages.
RO
Elect ht dehumid PI loop output.
RO
Convert ElectDehumPIOut to stages.
RO
Effective outdoor relative humidity.
RO
Effective space relative humidity.
RO
OA enthalpy using OAT and OA humidity.
RO
IA enth using space temp and IA humid.
RO
Current humidity status of space.
M
Keypad dehumidification enable.
RO
Specifies if dehumidification is avail.
RO
Keypad or network dehumid enabled.
RO
Network outside relative humidity.
RO
Network space relative humidity.
RO
Seconds since state change occurred.
RO
Seconds since pump was turned on.
RO
Room sensor mode status.
RO
Room sensor fan speed status.
T
Remote sensor setpt adj type.
RO
Current password level
N
Enter a new password.
M
Current keypad On/Stop password level.
U
Clear the password level to NONE.
-
Password countdown timer.
Uses LUIs GetText function with Index parameter to return one of up to 32
RO
alarms.
RO
Active alarm status.
U
Keypad reset alarms.
RO
Tenant override reset alarms.
Uses LUIs GetText function to return a whole screens-worth of data. Returns the
following: Alarms|Active
RO
For Tech Support call 800-432-1342 or www.daikinapplied.com
RO
Cause of Configurable Alarm.
RO
Control board hardware alarm status.
RO
Active when a comp alarm is active.
Uses LUIs GetText function with Index parameter to return one of up to 32
RO
alarms.
Uses LUIs GetText function to return a whole screens-worth of data. Returns the
following: Alarms|Active
RO
For Tech Support call 800-432-1342 or www.daikinapplied.com
66
www.DaikinApplied.com