Daikin MicroTech Operation And Maintenance page 43

Unit ventilator controls for applied classroom unit ventilators
Table of Contents

Advertisement

Terminal
DO1
DO2
DO3
DO4
DO5
DO6
DO7
DO8C
DO8-NO
DO8-NC
DO9, 10, 11 C
DO9
DO10
DO11
DO12, 13, 14 C
DO12
DO13
DO14
www.DaikinApplied.com
Software I/O
Binary Outputs
DO1
DO2
DO3
DO4
DO5
DO6
DO7
24VAC or Dry Contact Common
DO8
DO8
24VAC or Dry Contact Common for 3 outputs
DO9
DO10
DO11
24VAC or Dry Contact Common for 3 outputs
DO12
DO13
DO14
43
Signal Type
24VAC Output
24VAC Output
24VAC Output
24VAC Output
24VAC Output
24VAC Output
24VAC Output
Normally Open Output
Normally Closed Output
24VAC or Dry Contact Output
24VAC or Dry Contact Output
24VAC or Dry Contact Output
24VAC or Dry Contact Output
24VAC or Dry Contact Output
24VAC or Dry Contact Output
OM 1280-2 • MICROTECH UNIT CONTROLLER
Trending
UV Function
Fan Low/ECM Signal
Fan Medium
Fan High
Reversing Valve/
2 Position Heating Valve
Fault Indication
Outdoor Fan Signal
Exhaust Fan Signal/Auxillary Heat
24VAC or Dry Contact Common
Pump or Motorized Valve NO
Pump or Motorized Valve NC
Electric heat 24VAC Common
Electric Heat Stage 1
Electric Heat Stage 2
Electric Heat Stage 3
24VAC Common
Compressor 1/2 position Cooling Valve
Compressor 2
Drain Pan Heater

Advertisement