Daikin MicroTech Operation And Maintenance page 69

Unit ventilator controls for applied classroom unit ventilators
Table of Contents

Advertisement

Menu Name
Minimum Password to Read
(Menu Index)
(None, User, Manager, Technician)
EconPropGn:
EconIntgGn:
CO2PropGn:
CO2IntgGn:
TemperDiff:
TemperEn:
OAMnPosExIlck:
EOCLowOASpt:
RstMnVlts:
RstMxVlts:
RstMnUnits:
RstMxUnits:
SZnVAVMxDelta:
SZnVAVMnFan:
SZnVAVMxFan:
SZnVAVPropGn:
SZnVAVIntgGn:
OADLLPropGn:
OADLLIntgGn:
OADLLInitPos:
OADLLPiDltOut:
SpcCO2En:
OADCloseDly:
RstMnCO2:
RstMxCO2:
Set|FaceBypassDampr
FBDPropGn:
FBDIntgGn:
FBStrkTm:
EWTFbAlrDly:
FBPMinPos:
Set|ServerClient
SClntType:
Set|HydroHeating
HtWtrPI:
HtPropGn:
HtIntgGn:
HtgMnPos:
HtMxDeltTmp:
HtMxPos:
CfgEwtRetryTime:
Set|HydroCooling
ColdWtrPI:
ClPropGn:
ClIntgGn:
ClMnPos:
ClMxDeltaTmp:
ClMxPos:
Set|ExhaustFan
ExhStrtPos:
www.DaikinApplied.com
Minimum Password to Write
(None, User, Manager, Technician)
"RO" if Read Only
T
T
T
T
N
N
N
N
T
T
T
T
T
T
T
T
T
T
T
T
T
N
N
T
T
T
T
T
T
T
T
N
T
T
T
T
T
T
N
T
T
T
T
T
N
Appendix – Local User Interface (LUI)
Help Text
T
Economizer proportional gain.
T
Economizer integral gain.
T
CO2 proportional gain.
T
CO2 integral gain.
T
Air tempering mode differential.
M
Air tempering mode enable.
T
Min OAD when exhaust interlock active.
T
EOC valve open if OAT<spt and FBPD clsd.
T
aiCO2 at this val then reset RstMnVlts.
T
aiCO2 at this val then reset RstMxVlts.
T
PI out when aiCO2 is at RstMnVlts.
T
PI out when aiCO2 is at RstMxVlts.
T
Single zone VAV max delta.
T
PI loop: Single zone VAV min fan.
T
PI loop: Single zone VAV max fan.
T
Single zone VAV proportional gain.
T
Single zone VAV integral gain.
T
OAD lower limit proportional gain.
T
OAD lower limit integral gain.
T
Initial lower limit OAD position.
T
Lower limit OAD PI calculation.
T
Space CO2 enable.
T
Damper close after fan off delay.
T
aiCO2 at this val then reset cpResetMinUnits.
T
aiCO2 at this val then reset cpResetMaxUnits.
T
Face & bypass damper proportional gain.
T
Face & bypass damper integral gain.
T
Time for FBP damper to swing open.
T
Alarm delay if EffEWT not suitable for F&BP
T
Face bypass min position.
T
Server Client Configuration.
RO
Hot water PI loop output.
T
Hydro htg valve proportional gain.
T
Hydro htg valve integral gain.
T
Output when temp delta is 0.
T
Cntl and target delta for vlv at 100%.
T
Output when delta is max delta temp.
T
Delay before retrying opening valve.
RO
Cold water PI loop output.
T
Hydro clg valve proportional gain.
T
Hydro clg valve integral gain.
T
Output when temp delta is zero.
T
Cntl and target delta for vlv at 100%.
T
Output when delta is max dlta temp.
T
Energize Exh fan OAD position setpt.
69
OM 1280-2 • MICROTECH UNIT CONTROLLER