Daikin MicroTech Operation And Maintenance page 64

Unit ventilator controls for applied classroom unit ventilators
Table of Contents

Advertisement

Table 29: Local User Interface (LUI) Parameters
Menu Name
Minimum Password to Read
(Menu Index)
(None, User, Manager, Technician)
Live
MSM:
CntrlTmp:
EffSpt:
EffectOcc:
PWLevel:
EnterPW:
ClearPW:
UnitStatus
MSM:
MSM:
Prev1MSM:
Prev2MSM:
Prev3MSM:
Prev4MSM:
AppModeCmd:
KeyAppMode:
EffectHtCl:
EnergHold:
NetEnrgHld:
KeyEnrgHld:
NetEmergOv:
KeyEmergOv:
AllowHeat:
AllowCool:
AllowDehum:
RONgtPrgTmr:
EffHtClNn:
AuxHt:
EmergOvRes:
OnStop:
LowOAFrzStat:
ValveFrzProt:
CondOverflw:
Occupancy
EffectOcc:
KeyOccManCmd:
NetOccManCmd:
NetOccSensor:
NtOccSched:
TenantOver:
Temperatures
SpaceTemp:
RAT:
CntrlTmp:
OAT:
DAT:
EffEWT:
LWT:
InAirCoilDx:
OutArCoilDx:
CntrlTmpSt:
NetSpcTemp:
NetOAT:
NetEWT:
Setpoints
EffSpt:
NetSetpt:
Setpoint:
ClgSpt:
HtgSpt:
SetptOffset:
LocSptShft:
ClgSptOffst:
HtgSetptOffst:
NtSptOffst:
NtOccClSptSh:
NtStdClSptSh:
OM 1280-2 • MICROTECH UNIT CONTROLLER
Minimum Password to Write
(None, User, Manager, Technician)
"RO" if Read Only
T
N
N
N
N
N
N
T
N
T
T
T
T
N
N
N
N
N
N
N
N
T
T
T
N
N
N
N
N
T
T
T
N
N
N
N
N
N
N
T
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
Appendix – Local User Interface (LUI)
Help Text
RO
Main State Machine (MSM) state.
RO
Selected temp, either space or RAT.
RO
Effective setpoint
RO
Actual occupancy mode of unit.
RO
Current password level.
N
Enter a new password.
U
Clear the password level to NONE.
RO
Main State Machine (MSM) state.
Main State Machine (MSM) state. Duplicate of MSM parameter. Displayed as
RO
enumerated text.
RO
Previous 1 Main State Machine state.
RO
Previous 2 Main State Machine state.
RO
Previous 3 Main State Machine state.
RO
Previous 4 Main State Machine state.
RO
System status command.
U
Keypad heat/cool command.
RO
Actual heat/cool mode of unit.
U
Energy hold-off status.
RO
Energy hold-off network command.
U
Energy hold-off keypad command.
RO
Network emergency override.
M
Keypad emergency override.
RO
Heating allowed status.
RO
Cooling allowed status
RO
Dehumidification allowed status.
RO
Night purge count down timer.
RO
Mode is: Heat, Cool or None.
RO
Aux heat on/off status.
RO
Emergency override result.
RO
Keypad On/Stop status.
RO
Actv when OAT < EOCLowOASpt.
RO
Actv if LowOAFrzStat Actv and F&B clsd.
RO
Condensate overflow status.
RO
Actual occupancy mode of unit.
U
Keypad occupancy override command.
RO
Network occupancy override command.
RO
Network occupancy sensor.
RO
Network occupancy schedule command.
RO
Tenant Override start trigger.
RO
Current space temperature.
RO
Analog input return/room air temp.
RO
Selected temp, either space or RAT.
RO
Outside air temperature.
RO
Discharge air temperature.
RO
Entering Water Temperature.
RO
Leaving Water Temperature.
RO
Indoor air/DX coil temperature.
RO
Outdoor air/DX coil temperature.
RO
Cool, heat, between or invalid.
RO
Network space temperature.
RO
Network outside air temperature.
RO
Network Entering Water Temperature.
RO
Effective setpoint
RO
Network setpoint.
RO
Current setpoint.
RO
Current cooling setpoint
RO
Current heating setpoint
RO
Setpoint offset.
RO
Local hardwired setpt shift.
RO
Current calculated clg setpoint offset
RO
Current calculated htg setpoint offset
RO
Network setpoint offset.
RO
Net Occupied cooling setpoint shift.
RO
Net Standby cooling setpoint shift.
64
Appendix – Local User Interface (LUI)
www.DaikinApplied.com