UVC Inputs and Outputs
Table 22: UVC Inputs and Outputs
Terminal
H2-1
H2-2
H3-1
H3-2
H3-3
H3-4
H4-1
H4-2
H5-1
H5-2
H5-3
H5-4
H6-1
H6-2
H6-3
H6-4
H6-5
H6-6
H6-7
H6-8
H7-1
H7-2
H7-3
H8-1
H8-2
H8-3
H9-1
H9-2
H9-3
H9-4
H10-1
H10-2
H10-3
H10-4
H11-1
H11-2
H11-3
H11-4
H11-5
H12-1
H12-2
H12-3
OM 1280-2 • MICROTECH UNIT CONTROLLER
Software I/O
PWM 1
PWM 2
Analog Outputs
AO 1
AO 2
AO 3
AO 4
Binary Inputs
BI 5
BI 6
BI 1
BI 2
BI 3
BI 4
Room Sensor Inputs
BI 7
BI 8
BO Status LED
AI 1
AI 2
AI 3
AI 4
Analog Inputs
AI 5
AI 6
AI 7
AI 8
AI 9
AI 10
AI 11
AI 12
AI 13
AI 14
AI 15
AI 16
Signal Type
PWM
80Hz Cycle
80Hz Cycle
0-10VDC Out
0-10VDC Out
0-10VDC Out
0-10VDC Out
Discrete BI
Discrete BI
24VAC BI
24VAC BI
24VAC BI
24VAC BI
Discrete BI
Discrete BI
Binary Output
0-1.5K Pot
0-1.5K Pot
0-1.5K Pot
10K Type II Thermistor
GND
5VDC
0-5 VDC Signal
GND
5VDC
0-5 VDC Signal
GND
10K Type II Thermistor
GND
10K Type II Thermistor
GND
10K Type II Thermistor
GND
10K Type II Thermistor
GND
10K Type II Thermistor
GND
10K Type II Thermistor
GND
Conductivity
0-10VDC Input
0-10VDC Input
0-10VDC Input
42
UVC Inputs and Outputs
UV Function
Supply Fan
OA Damper
F&B Damper
Modulating Cooling Valve
Modulating Heating Valve
Boilerless Indication
Ventilation Lockout
High Pressure
Freeze Stat
Configurable
Configurable
Occupancy
Shutdown
Status LED
Setpoint
Unit Mode
Fan Speed
Space Temperature
GND
Sensor Power
Indoor Humidity Signal
Sensor Ground
Sensor Power
Outdoor Humidity Signal
Sensor Ground
Discharge Air Temperature
Sensor Ground
Return Air Temperature
Sensor Ground
Outdoor Air Temperature
Sensor Ground
Outdoor Coil Refrigerant/
Entering Water Temperature
Sensor Ground
Leaving Water
Sensor Ground
Indoor Coil Refrigerant/Suction Refrigerant Temperature
Sensor Ground
Condensate
CO
/VOC
2
www.DaikinApplied.com