Mandik FDMR 60 Manual page 21

Hide thumbs Also See for FDMR 60:
Table of Contents

Advertisement

Position:
1
Fire damper
2
Gypsum plate
3
Mineral wool (type depending on the type of construction)
4
Mortar or gypsum
5
Duct
Position:
1
Fire damper
2
Gypsum plate
3
Mineral wool (type depending on the type of construction)
4
Stuffing box (mineral stone wool min. density 140 kg/m³)
5
Fire protection mastic min. thickness 1 mm
≥ 40
Installation opening has to
be reinforced by profile
(UW, CW). Profil is fixed by
screws ≥3,5 mm with corre-
sponding length. Distance
between screws ≤200 mm.
≥ 50
≥ 25
Used materials - example:*
4
Promapyr, Rockwool Steprock HD, Hilti CFS-CT B 1S 140/50
5
Promastop - P, K, Hilti CFS-CT
21
5
* Fire resistant insulation and fire resistant board can be
replaced by another approved fire sealing system for
damper installation with equivalent material properties.
Installation opening has to
be reinforced by profile
(UW, CW). Profil is fixed by
screws ≥3,5 mm with corre-
sponding length. Distance
between screws ≤200 mm.
≥ 100
≥ 100