Position:
1
Fire damper
2
Solid ceiling construction
3
Mortar or gypsum
4
Duct
4
≥ 25
≥ 50
Position:
1
Fire damper
2
Solid ceiling construction
3
Stuffing box (mineral stone wool min. density 140 kg/m³)
4
Fire protection mastic min. thickness 1 mm
*
≥ 40
*
24
* min. 110 - Concrete/ min. 125 - Aerated concrete
* min. 110 - Concrete/ min. 125 - Aerated concrete
Used materials - example:**
3 Promapyr, Rockwool Steprock HD, Hilti CFS-CT B 1S 140/50
4 Promastop - P, K, Hilti CFS-CT
** Fire resistant insulation and fire resistant board can be