Huawei UPS5000-E-BF Series User Manual page 40

Advertisement

UPS5000-E-(25 kVA-75 kVA)-BF
User Manual
Silk Screen
STATUS_0V
SWITCH
STATUS_BP
SWITCH
STATUS_0V
SPD
0V
Functions
The dry contact card allows the UPS to detect and manage the switch status of the battery
system (including the external battery switch) and implement remote emergency power-off
(EPO).
Specifications
Issue 07 (2019-12-13)
Description
Port for monitoring the
bypass input circuit breaker
Port for signal ground
Port for monitoring the input
AC surge protective device
(SPD)
Port for signal ground
The dry contact interface card takes effect only after it is set on the monitoring system. Set the
unused dry contact signal to the unused status.
Set the EPO port to NO or NC as required.
When multiple UPSs are paralleled, all dry contact signals to be used need to connect to each UPS.
Single cables require dual-insulated twisted cables. If the length of a power cable is within 25–50 m,
its cross-sectional area must be 0.5 mm
Hot-swappable
0.5 U high
Copyright © Huawei Technologies Co., Ltd.
Status
Connected: circuit
breaker ON
Disconnected:
circuit breaker
OFF
Connected: SPD
enabled
Disconnected:
SPD disabled
2
2
to 1.5 mm
.
2 Overview
Initial Status
Connected
Connected
31