UPS5000-E-(25 kVA-75 kVA)-BF
User Manual
Set Battery capacity correctly after double check. Incorrect settings affect the charging
power.
High or low charging power tends to shorten the battery lifespan, or even damages
batteries. To seek help about how to determine the battery capacity, contact Huawei
technical support.
When battery strings are shared, the battery capacity of each UPS is the total capacity of
battery strings. When no battery string is shared, the battery capacity of each UPS is the
capacity of battery strings connected to the single UPS. For example, if forty 9 Ah/12 V
batteries are connected in series and two battery strings are connected in parallel to the
UPS, the Battery capacity is 9 Ah + 9 Ah = 18 Ah.
Figure 5-1 Settings Wizard
Table 5-2 Battery capacity settings
Battery Specifications
Issue 07 (2019-12-13)
Set the time and date correctly. Incorrect time and date will cause false fault analysis during
maintenance or repair.
After you set network parameters, connect the UPS to the network over a network cable, which
enables you to remotely manage the UPS. If you do not need remote management, retain the default
network parameter settings.