Download Print this page

Huawei UPS5000-E-BF Series User Manual page 176

Advertisement

UPS5000-E-(25 kVA-75 kVA)-BF
User Manual
Battery Specifications
9 Ah/12 V
9 Ah/12 V
9 Ah/12 V
Step 2 After you set parameters on the Settings Wizard screen, the MDU displays the Bypass mode
and No battery alarms, which do not need to be handled. If there is any other alarm, you need
to rectify the fault.
Step 3 View the system running diagram on the MDU to check that the UPS is working in bypass
mode.
----End
Online Startup
Step 1 Insert a WiFi module into the USB port on the MDU.
Step 2 Enable the mobile phone WLAN, search for the UPS WiFi signal, and connect to the WiFi
signal. The default value of WiFi SSID is UPS_WiFi.
Issue 07 (2019-12-13)
After you set parameters on the Settings Wizard screen, choose System Info > Settings >
Advanced Param. Check that System Capacity, Power module capacity, Requisite modules, and
Redundant modules match the actual values.
If dry contact signals are connected to the system, choose System Info > Settings > Dry contacts
and check that the connected dry contacts have been enabled and that the disconnected dry contacts
have been disabled.
If you do not need to use the app to start the inverter, choose System Info >
Maintenance > Inv. ON on the MDU.
The Service Expert
Android. User interfaces displayed in this document correspond to the app version
V100R001C00B055 and are for reference only.
For offline startup, enter the barcode and the verification code on the mobile phone app.
The app automatically generates a startup password for the UPS. Then enter the password
on the MDU screen to start the UPS.
For online startup, activate the startup password on the mobile phone app to start the UPS.
If the initial startup verification passes, startup verification is not required afterwards.
After factory settings are restored, re-verification for startup is required.
Copyright © Huawei Technologies Co., Ltd.
Number of Battery
Strings
Two battery strings
connected in parallel
Three battery strings
connected in parallel
Four battery strings
connected in parallel
app can be downloaded from Google Play and can run on
5 Operations
Battery Capacity
9 Ah + 9 Ah = 18 Ah
9 Ah + 9 Ah + 9 Ah = 27
Ah
9 Ah + 9 Ah + 9 Ah + 9 Ah
= 36 Ah