Operating Guide | VLT® FCD 300 PROFIBUS Converter MCA 117

5.5 FCD 300 Parameter Group 4

5.5.1 Conversion of Parameter 400 Brake Function
Table 110: Parameter 400
FCD 300 series
Parameter
400 Brake Function
Options
[0] Off
[1] Resistor
[4] AC Brake
5.5.2 Conversion of Parameter 405 Reset
Table 111: Parameter 405
Parameter
Options
5.5.3 Conversion of Parameter 406 Automatic Restart Time
Table 112: Parameter 406
FCD 300 series
Parameter
406 Automatic Restart Time
Range
0–10 s
56 | Danfoss A/S © 2019.11
FCD 300 series
405 Reset
[0] Manual Reset
[1] Automatic Reset x 1
[3] Automatic Reset x 3
[10] Automatic Reset x 10
[14] Reset At Power Up
FCD 302 series
2-10 Brake Function
2-17 Over-voltage Control
Parameter 2-10 = [0] Off
Parameter 2-17 = [0] Off
Parameter 2-10 = [1] Resistor Brake
Parameter 2-17 = [0] Off
Parameter 2-10 = [0] Off
Parameter 2-17 = [2] Enabled
FCD 302 series
14-20 Reset Mode
[0] Off
[1] Automatic Reset x 1
[3] Automatic Reset x 3
[10] Automatic Reset x 10
[11] Reset At Power Up
FCD 302 series
14-21 Automatic Restart Time
0–600 s
Parameter Mapping Lists
AQ289550754901en-000101 / 130R0890