SmartLi-80Ah
User Manual
Tools and Meters
3.1.3 Preparing Power Cables
Table 3-2 Recommended cross-sectional areas for power cables
Item
Battery
3.1.4 Unpacking and Checking
Context
Issue 02 (2020-05-17)
Table 3-1 lists only the common tools for installation and cable connection. For more dedicated tools
required, see the corresponding component manuals. Prepare tools based on site requirements.
Recommended
cross-sectional
2
area (mm
)
When selecting, connecting, and routing power cables, follow local safety regulations
and rules.
When the external conditions change, for example, the cable layout or ambient
temperatures, perform verification in accordance with the IEC-60364-5-52 or the local
regulations.
Cable type: single-core 90° C soft power cable with a copper conductor.
Copyright © Huawei Technologies Co., Ltd.
Description
+
120 (The load of a single battery cabinet is less
than or equal to 150 kW, you are advised to set
N
the I1 value of the battery circuit breaker to the
MIN value.)
-
150 (The load of a single battery cabinet is
greater than 150 kW.)
PE
70
3 Installation
29