Huawei does not provide the EPO switch or cable. If the cable is required, the
recommended cable is 22 AWG.
Equip the EPO switch with a protective cover to prevent misoperations, and cover the
cable with protective tubing.
Connect the EPO button to the EPO port on the SmartLi using the cable.
Figure 3-25 Cable connection for an NO EPO switch
Figure 3-26 Cable connection for an NC EPO switch
Issue 02 (2020-05-17)
When the EPO switch is in the NC state, remove the jumper between EPO_NC and EPO_12V
before connection. When the EPO switch is turned off, EPO is triggered.
When the EPO switch is in the NO state, ensure that the jumper is connected between EPO_NC and
EPO_12V. When the EPO switch is turned on, EPO is triggered.