SmartLi-80Ah
User Manual
Alarm ID
Alarm Name
(Alarm
ID-Cause
ID)
Battery module
0612-1
fault
Battery module
0612-2
fault
0021-5
Battery EOD
Issue 02 (2020-05-17)
Severity
Cause
Critical
Critical
Critical
The battery
voltage reaches
the EOD
threshold due to
continuous
Copyright © Huawei Technologies Co., Ltd.
A
Solution
The sampling
Replace the faulty battery module.
connecter is
not firmly
connected.
The board
sampling
circuit of the
battery
module is
faulty.
The battery
module is
faulty.
The sampling
Replace the faulty battery module.
connecter is
not firmly
connected.
The board
sampling
circuit of the
battery
module is
faulty.
The battery
module is
faulty.
1. Check the status of the battery
cabinet and turn on the BCB
switch.
2. Check the mains and charge
batteries in a timely manner.
A Alarm List
Alarm List
99