FireClass FC503 Installation Manual page 45

Addressable fire control panels
Hide thumbs Also See for FC503:
Table of Contents

Advertisement

Alphanumeric keypad
Use the alphanumeric keypad to enter the number of SC
output.
Cursor keys
Table 44: Cursor key functions in choose output
Key
Function
Up
Use to show the next output
category (SC-OC)
Down
Use to show the previous output
category
Right
No function
Left
No function
ESC and ENTER keys
Table 45: ESC and ENTER key function in smoke delay
Key
Function
ESC
Use to cancel the operation and
return to the previous screen
Use to accept the selection,
ENTER
activate the output selection, and
activate the loop device
programming screen if the output
exists. Otherwise a warning screen
is displayed for 5 seconds
"WRONG VALUE! Enter the
parameter again". After 5 seconds
the user interface moves back to
the screen for selecting the outputs.
Once the output has been programmed, including type and
identification number, and the ENTER key is pressed to
accept the selection, enter the label for the output.
SET AS SC1
When set as YES, the relevant output will behave as the
Sounder Circuit 1 (SC1). This allows redundant output
circuits to drive site sounders. The default setting is NO.
Setting the option to YES will end the programming
sequence for that output.
Note: The panel on board Open Collector outputs (OC1,
OC2) may not be programmed to act as SC1.
PANEL ALARM TRIGGER?
When the PANEL ALARM TRIGGER? option is set to
YES, the relevant output becomes active on the panel alarm
condition. Alternatively, a more specific trigger condition
may be defined for the output. The default setting is YES.
DISABLEMENT TRIGGER?
The DISABLEMENT TRIGGER? option activates the
relevant output if any system part is disabled. The default
setting is NO.
Note: This parameter is made available only if the
parameter PANEL ALARM TRIGGER for the same output
is set to NO. Setting the parameter to YES will end the
programming sequence for that output. Outputs which
have this option programmed will not be silenceable.
This feature is also available for Panel FIRE relay and
FC410RIM, FC410SIO, FC410MIO, FC410QMO,
FC410QRM, FC410QIO loop modules.
OUTPUT NAME
TRIGGER ZONE 1
TRIGGER ZONE 2
TRIGGER EVENT
SILENCEABLE
MONOSTABLE
Figure 28: Programming SC active on disablements
1
Control panel name
2
Output number
3
Access level
4
Control panel status
5
If blinking, control panel working
properly
6
Output type
7
Output number
8
Insert output label
45