Cursor keys
Table 38: Cursor key functions in SW zone
Key
Function
Up
No function
Down
No function
Right
Use to select the next available SW
zone
Left
Use to select the previous available
SW zone
ESC and ENTER keys
Table 39: ESC and ENTER key function in SW zone
Key
Function
ESC
Use to delete the procedure and
return to the previous screen
ENTER
Use to accept the SW zone
selection and activate the loop
device programming screen
If the SW zone does not exist, the following warning
screen is displayed for 5 seconds: "WRONG VALUE!
Enter the parameter again". After 5 seconds the user
interface returns to the chosen SW zone screens.
Zone name
Enter the zone label (20 characters maximum) using the
alphanumeric entry procedures.
SW zone in WALK TEST
After selecting the SW zone, enable or disable the option
Zone in WALK TEST (OFF).
If the option All Devices (ALL) is selected, all the
devices assigned to the zone in the WALK TEST mode
will not generate an alarm if they are activated but will
reach the TEST status.
If the option detector (DET) is selected, only the
detectors assigned to the zone in the WALK TEST
mode will not generate an alarm in the case of their
activation but will reach the TEST status.
If the call points (CP) option is selected, only the call-
points assigned to zone in WALK TEST mode will not
generate alarm in the case of their activation but will
reach the TEST status. The presence of a zone in
WALK TEST mode is signaled by the TEST yellow
LED on the User Interface. More than one zone can
be put in WALK TEST mode at the same time.
In this phase the keypad and keys have the following
functions:
Alphanumeric keypad
No function is related to the alphanumeric keypad.
Cursor keys
Table 40: Cursor key functions in SW zone in WALK
TEST
Key
No function
Up
Down
No function
Right
Use to select the next ON-OFF-
ALL-det-CP
Use to select the previous ON-
Left
OFF-ALL-det-CP
ESC and ENTER keys
Table 41: ESC and ENTER key function in SW zone
Key
ESC
Use to delete the procedure and
return to the programming screen
ENTER
Use to accept the selection and
activate the corresponding
programming screen
Figure 26: Selecting and programming SW zone
1
Index of SW zone program
2
Access level
3
Control panel status
4
If blinking, control panel working
properly
5
Name of control panel
6
Select between ON or OFF
Sounders on (3s)
If YES, every test event (input activation) activates the
sounders in the same zone for 3 seconds.
SMOKE DELAY (60s/30min)
For each zone, program the delayed activation of smoke
detectors according to the following schedule:
If the smoke level exceeds the alarm threshold, the panel
does not signal anything at first.
After 60 seconds, if the smoke level is still above the
threshold, the system goes into alarm condition.
Otherwise, there are no signals.
Function
Function
43