The control panel is ready to work at this time with the
default basic programming.
Optionally, you can set the system addresses differently.
To set the system addresses differently, complete the
following steps:
1. Press the ENTER key, so the fire panel initiates the
MAPPING DEVICES phase.
2. In the MAPPING DEVICES phase, activate all the input
devices including detectors, input modules, and manual
call points in sequence. Return to the front of the fire
alarm control panel.
3. Report the sequence of activation on the map of
system. The fire panel will store the activation
sequence.
4. Use the user interface Up and Down keys to examine
the first activated device. Select the device. When the
device is selected, the address will blink. If necessary,
change the address. Press ENTER to confirm and the
address will become fixed.
Note: When Reset is running, the command keys are
inoperative. To switch to the programming phase of the
device, press the ENTER key again.
Second phase of auto-addressing
In the second phase, examine the sounders, the beacons,
and the output module.
Locate the devices by scanning the list of auto-addressed
devices.
When you reach an output-only device, the device
becomes active until a new device is selected or the
permanent address is entered. Activation is signaled by a
sounder starting to sound, a beacon starting to flash, or an
output module illuminating its LED.
Unique indicates that it is the only device of its type on the
loop. For example, if only one FC410DDM module is used
in the system, it is tagged as Unique and it is not
necessary to activate it if you know where it is.
Note: The enroll process does not take place until all of
the loop wiring issues have been resolved.
Use the auto-addressing procedure when there are NG1
devices on the loop or it has no effect. The device
mapping process does not take place until all of the double
address faults have been removed.