External Battery Cabinet Connection Precautions

Battery
1. Charge Voltage
2. Charge Current
Only use the same type of batteries from the same supplier. Never use old, new and differ-
ent Ah batteries at the same time.
The number of batteries must meet UPS requirements.
Do not connect the batteries in reverse.
Use the voltage meter to measure whether the total voltage, after the external battery cabi-
net connection, is around 12.5Vdc × the total number of batteries.
To extend battery backup time, you can connect several external battery cabinets to the
UPS. Please note that the number of the batteries in each paralleled external battery cabi-
net must be the same.
Ultron HPH Series UPS
WARNING:
You can connect loads to the UPS only after the batteries are fully charged. This
ed when a power failure occurs.
UPS
20kVA
30kVA
40kVA
NOTE:
1. You can follow actual need to adjust the charge current from the minimum to
the maximum. Each adjustment level is 0.5A.
2. If you need to modify the charge current default setting and low battery shut-
down default setting, please contact your local dealer or service personnel.
Default
Minimum
2A
5A
5A
42
Maximum
1A
1A
1A
-
5A
9A
9A