9 - LOADING THE DEFAULT PARAMETERS
If necessary, it is possible to restore all parameters to their standard or default values (see the final summary table).
PLEASE NOTE: This procedure results in the loss of all customised parameters, and hence it has been included outside the
configuration menu, in order to minimise the likelihood of it being run in error.
Loading of the default parameters is performed each time the initialisation procedure is performed (even without working
time self-training).
The parameters acquired during initialisation are maintained, even when the default parameters are loaded.
1. Press and hold the OK key until the display shows -dEF
2. Release the OK key: the display shows ESC (only press the OK key if it is desired to exit this menu)
3. Press the i key: the display shows dEF.
4. Press the OK key: the display shows no
5. Press the i key: the display shows Si
6. Press the OK key: all parameters are overwritten with their default values (see the table on pages 74-75), the control units exits
programming mode and the display shows the control panel.
51