Ntp-A119 Install The Alarm Expansion Panel, Page - Cisco ONS 15454 Install

Install the shelf and backplane cable
Hide thumbs Also See for ONS 15454:
Table of Contents

Advertisement

Chapter 1 Install the Shelf and Backplane Cable
Figure 1-1
Continue with the
Step 4
to install an alarm expansion panel (AEP). If not, continue with the
Timing, LAN, and Craft Pin Connections" procedure on page
Stop. You have completed this procedure.
NTP-A119 Install the Alarm Expansion Panel
Purpose
Tools/Equipment
Prerequisite Procedures
Required/As Needed
78-18537-01
Installing the Fan-Tray Assembly
Fan tray
assembly
LCD
"NTP-A119 Install the Alarm Expansion Panel" procedure on page 1-13
This procedure installs an alarm expansion panel (AEP) onto the
15454-SA-ANSI or 15454-SA-HD shelf backplane. The AEP provides
alarm contacts in addition to the 16 provided by the AIC-I card. Typically,
the AEP is preinstalled when ordered with the ONS 15454; however, the
AEP can be ordered separately. The AIC-I card must be installed before
you can provision the alarm contacts enabled by the AEP.
#2 Phillips screwdriver
Medium slot-head screwdriver
Small slot-head screwdriver
Wire wrapper
Standoffs (4)
DLP-A10 Remove the Lower Backplane Cover, page 17-10
As needed
NTP- A119 Install the Alarm Expansion Panel
"NTP-A8 Attach Wires to Alarm,
1-16.
Cisco ONS 15454 Procedure Guide, Release 8.5.1
if you plan
1-13

Advertisement

Table of Contents
loading

Table of Contents