scp <filename> <user>@< IP address of PDU>:
Note:
(5) The SSH setting on the PDU must be Enabled.
(6) <filename> is the filename of the firmware file. There are two firmware files to upload:
cpsmpdumbfw_XXX.bin and cpsmpdumbdata_XXX.bin. In order to upgrade the firmware
version both files need to be uploaded. Only one firmware file can be uploaded at a time, it is
recommended to upload the firmware file cpsmpdumbfw_XXX.bin first followed by the data file
cpsmpdumbdata_XXX.bin.
(7) <user> is the username of the SSH account on the PDU.
(8) Ensure to add ":" after the IP address.
For example:
scp cpsmpdumbfw_XXX.bin cyber@192.168.1.100:
Note: cpsmpdumbfw_XXX.bin is the firmware file of the version being updated.
4. After executing the command, a message may appear asking if you trust the host. To continue type
"y" for yes within 10 seconds.
5. On the next screen enter the PDU password. The firmware file transfer may take a couple minutes
to complete. Please wait until the progress indicator displays 100%. The system will automatically
log out and reboot after the transfer is complete.
6. Repeat steps 3 through step 5 to upload the data file cpsmpdumbdata_XXX.bin to complete the
firmware update process.
7. If the firmware file transfer is unsuccessful you will see an error message. Attempt to retype the
command and execute it again.
3-Phase Intelligent PDU User Guide
Firmware Upgrade
93