CyberPower PDU33 Series User Manual page 26

3-phase intelligent pdu
Table of Contents

Advertisement

Item
Outlet Restriction**
Power Restore
Peak Load
Energy
ColdStart Configuration
ColdStart State
ColdStart Delay
System Configuration
Idle Time
**For some models, the Outlet Restriction only shows in the
3-Phase Intelligent PDU User Guide
When load current exceeds the corresponding threshold, no
outlets will be allowed to turn on.
*None: Users can turn on an outlet even if the device is in Near
Overload or Overload state.
*On Near Overload: Users cannot turn on an outlet when the
device is in Near Overload or Overload state.
*On Overload: Users cannot turn on an outlet when the device is
in Overload state.
Reset the peak load to zero.
Reset the energy to zero.
*Previous State: Outlets will return to the same state (on or off)
they were in prior to the PDU turning off. The ColdStart Delay
setting will apply when the PDU resumes power.
*All On: All outlets will turn on when power is restored to the PDU.
*Instant: Outlets will be turned on immediately when power is
restored to the PDU.
*Wait: Outlets will be turned on according to this setting when
power is restored to the PDU.
*Never: Outlets will not be turned on when power is restored to the
PDU.
The PDU LCD screen will turn off automatically after it remains
idle for the selected period of time.
Definition
Phase Manager
Page.
Web Interface
24