Item
Hysteresis
Rate of Change
Unit
Humidity
High Threshold
Low Threshold
Hysteresis
Rate of Change
Contact
3-Phase Intelligent PDU User Guide
The point where the environmental state changes from abnormal to
normal and users receive a clearing event notification. The function of
Hysteresis is to avoid receiving multiple event notifications.
*For high threshold, the point is the threshold minus the
Hysteresis value; for low threshold, the point is the threshold
plus the Hysteresis value.
For example: The high threshold is 32°C, and hysteresis is 2°C.
The temperature rises to 33°C, you will get a warning. Then
it goes down to 31°C and up to 33°C repeatedly. No clearing
events and warnings will occur while the temperature readings
are within the Hysteresis. You will not get a clearing event until
it drops to 30°C.
Define the abnormal change of temperature per 5 minutes.
For example: The current temperature is 23°C, and rate of
change is 10°C. If it goes up to 33°C or down to 13°C within 5
minutes, you will get a warning.
Select the unit of temperature.
Set the highest humidity value for a high humidity warning.
Set the lowest humidity value for a low humidity warning.
Same as Hysteresis under temperature.
Same as Hysteresis under temperature.
Enter the name of each input dry contact relay and use the dropdown
menu to define the normal status of each one.
Definition
Web Interface
9