Power Protection
The configurable load threshold can be set to prevent an overload condition. Coldstart and system
configurations are also offered for different user needs. See
Item
HOST/GUEST#
Load Configuration
Overload Threshold
Near Overload
Threshold
Low Load Threshold
3-Phase Intelligent PDU User Guide
PDU Tab > Manager > Device
Select the role of PDU (HOST or GUEST#) if PDUs are daisy
chained. Up to 3 GUEST PDUs can connect to 1 HOST PDU.
Set the value for the total wattage on the PDU that will signal an
overload warning. Must be higher than Near Overload Threshold
and equal to or lower than the PDU Rating in the
Set the value for the total wattage on the PDU that will signal a
near overload warning. Must be between Overload Threshold and
Low Load Threshold.
Set the value for the total wattage on the PDU that will signal a low
load warning. Must be lower than Near Overload Threshold.
PDU Tab > Device Manager.
Definition
Summary
Web Interface
Tab.