3000000000004000 - Server Temperature Error; Table 5: Server Environmental Conditions - Oracle E5-APP-B Alarms And Maintenance

Eagle lnp application processor
Hide thumbs Also See for E5-APP-B:
Table of Contents

Advertisement

Alarms and Maintenance
5. Contact
My Oracle Support (MOS)
in the previous steps.

3000000000004000 - Server Temperature Error

Alarm Type: TPD
Description: The internal temperature within the server is unacceptably high.
Severity: Major
OID: TpdTemperatureErrorNotify 1.3.6.1.4.1.323.5.3.18.3.1.2.15
Alarm ID: TKSPLATMA153000000000004000
Recovery
1. Ensure that nothing is blocking the fan's intake. Remove any blockage.
2. Verify that the temperature in the room is normal with the following table. If it is too hot, lower
the temperature in the room to an acceptable level.

Table 5: Server Environmental Conditions

Ambient Temperature
Ambient Temperature
Relative Humidity
Elevation
Heating, Ventilation, and Air Conditioning
Note: Be prepared to wait the appropriate period of time before continuing with the next step.
Conditions need to be below alarm thresholds consistently for the alarm to clear. The alarm may
take up to five minutes to clear after conditions improve. It may take about ten minutes after the
room returns to an acceptable temperature before syscheck shows the alarm cleared.
E76220 Revision 1, July 2016
for further assistance. Provide the syscheck output collected
Operating: 5 degrees C to 40 degrees C
Exceptional Operating Limit: 0 degrees C to 50
degrees C
Storage: -20 degrees C to 60 degrees C
Operating: 5° C to 35° C
Storage: -20° C to 60° C
Operating: 5% to 85% non-condensing
Storage: 5% to 950% non-condensing
Operating: -300m to +300m
Storage: -300m to +1200m
Capacity must compensate for up to 5100
BTUs/hr for each installed frame.
Calculate HVAC capacity as follows:
Determine the wattage of the installed
equipment. Use the formula: watts x 3.143 =
BTUs/hr