Xs814 Auxiliary Terminal Package; Xs830 Auxiliary Terminal Package; Xs831 Auxiliary Terminal Package - Honeywell Excel 800 SYSTEM Installation And Commissioning Instructions

Table of Contents

Advertisement

Excel 800

XS814 Auxiliary Terminal Package

Features
 Type: XS814 Auxiliary Terminal Package
 For mounting onto already-installed pluggable I/O
modules in order to equip them with additional terminals.
 Each unit consists of two terminal blocks (the "A" block
and the "B" block), each with seven terminals with a
maximum load of 12 A.
Fig. 94
XS814 Auxiliary Terminal Package
Terminal Assignment
A1
A2
A3
A4
A5
A6
A7
1
2
3
4
5
6
7
Fig. 95
Terminal assignment and internal connections of
XS814 Auxiliary Terminal Package

XS830 Auxiliary Terminal Package

Features
 Type: XS830 Auxiliary Terminal Package
 For mounting onto the top and/or bottom of already-
installed XF830A mixed I/O modules and the top of
already-installed XFU830A mixed I/O modules in order to
equip them with additional terminals.
 Each unit consists of two groups of terminal blocks
(the "A" block and the "B" block), each with nine
internally-connected push-in terminals with a maximum
load of 12 A.
A1 A2 A3 A4 A5 A6 A7 A8 A9
Fig. 96
XS830 Auxiliary Terminal Package
B1
B2
B3
B4
B5
B6
B7
1
2
3
4
5
6
7
B1 B2 B3 B4 B5 B6 B7 B8 B9
Terminal Assignment
A1
A2
A3
A4
A5
A6
1
2
3
4
5
Fig. 97
Terminal assignment and internal connections of
XS830 Auxiliary Terminal Package

XS831 Auxiliary Terminal Package

Features
 Type: XS831 Auxiliary Terminal Package
 For mounting onto the top and/or bottom of already-
installed XF830A mixed I/O modules and the top of
already-installed XFU830A mixed I/O modules in order to
equip them with additional terminals.
 Two groups of four pairs of push-in terminals (A1B1,
A2B2, ... A8B8, each with a 499Ω resistor) for converting
0...20 mA signals (maximum load per resistor = 25 mA)
into 0...10 Vdc signals, and one push-in ground terminal
per group. See also Fig. 89 and Fig. 90.
Note
The ground side of each of the eight incoming 0...20 mA
signals (A1B1, A2B2, ... A8B8) must be connected to a
ground terminal.
A1 B1 A2 B2 A3 B3 A4 B4 G1
Fig. 98
XS831 Auxiliary Terminal Package
Terminal Assignment
A1 B1 A2 B2 A3 B3 A4 B4 G1
1
2
3
4
5
Fig. 99
Terminal assignment and internal connections of
XS831 Auxiliary Terminal Package
65
Description of Extra Parts
A7 A8 A9
B1
B2
B3
B4
6
7 8 9
1
2
3
4
A5 B5 A6 B6 A7 B7 A8 B8
A5 B5 A6 B6 A7
6
7 8 9
1
2
3
4
EN1B-0375GE51 R0910
B5
B6
B7 B8 B9
5
6
7 8 9
G2
B7
A8
B8 G2
5
6
7 8 9