Excel 800

Planning

Overview

Engineering with CARE
During CARE engineering, the type of I/O modules, terminal
assignment and module configuration are defined
depending on the application.
Planning
In this step, the following has to be defined, if applicable:
 Power supply
 Fusing
 Earth grounding
 Lightning protection
 Panel Bus wiring
 Design of a L
W
ON
ORKS
 Design of a C-Bus network
 Useful accessories
 Cable selection
network

Transformer Selection

Note
In Europe the system transformer(s) must be safety isolating
transformers according to IEC61558-2-6.
In the U.S.A. and Canada, NEC Class-2 transformers must
be used.
Power Consumption
When selecting the appropriate transformer, take into
account the number of individual modules, accessories, and
field devices in determining the total power consumption.
Devices powered
XCL8010 with XI582
(backlight ON) and with
watchdog load (max. 500 mA)
XCL8010 with XI582
(backlight ON) but without
watchdog load
...821
...822
...823
...824
...825
XF830A
XFU830A
Table 10 Power consumption of Excel 800 System
components depending on power supply
Connectable Power Supplies
Honeywell CRT Series (Europe)
Transformer
Primary side
CRT 2
220/230 VAC
CRT 6
220/230 VAC
CRT 12
220/230 VAC
Table 11 Honeywell CRT series transformers data
9
Planning
Power consumption
24 VAC
24 VDC
690 mA
640 mA
190 mA
140 mA
130 mA
80mA
160 mA
90 mA
180 mA
130 mA
140 mA
90 mA
140 mA
90 mA
200 mA
95 mA
200 mA
95 mA
Secondary side
24 VAC, 50 VA, 2 A
24 VAC, 150 VA, 6 A
24 VAC, 300 VA, 12 A
EN1B-0375GE51 R0910