The L
W
Bus is a 78-kilobit serial link that uses
ON
ORKS
transformer isolation so that the bus wiring does not have a
polarity. I.e. it is not important which of the two L
Bus terminals are connected to each wire of the twisted pair.
The L
W
Bus does not need to be shielded on the
ON
ORKS
controller module side.
The L
W
Bus can be wired in daisy chain, star, loop
ON
ORKS
or any combination thereof as long as the maximum wire
length requirements are met.
Configuration
The recommended configuration is a daisy chain with two
bus terminations. This layout allows for max. L
Bus lengths, and its simple structure presents the least
number of possible problems, particularly when adding on to
an existing bus.
See also "L
W
Mechanisms", Product Literature no.:
ON
ORKS
EN0B-0270GE51.

C-Bus Topologies

Via the C-Bus up to 30 C-Bus devices (e.g., controllers, etc.)
can communicate with one another and a PC central. The
C-Bus must be connected via the individual controllers
(open ring).
Note
Star connection is not allowed because uncontrollable line
reflections may occur.
Instead of an Excel 800 Controllers, other C-Bus controllers
(e.g., the Excel 500, Excel 100, Excel 50) can also be
connected.
Fig. 4
C-Bus topology Excel 5000

Accessories

Besides the auxiliary parts of Table 5 on page 7, the
following accessories are available.
W
ON
ORKS
Preconfigured Connection Cables
Type
XW882
XW582
+ XW586
W
ON
ORKS
XW884
XW885
XW585
+ XW586
XW586
Table 14 Preconfigured connection cables
XW882 Cable Details
RJ45 plug with clip at front
Fig. 5
XW884 Cable Details
RJ45 plug with clip at front
Fig. 6
11
Connecting XCL8010
Controller with
XI582 Operator Interface
XI582 Operator Interface
Adapter cable for Excel
500/600 Controllers
Laptops
Laptops
Modems
SHIELD
+5V
XW882
XCL8010/XI582 cable details
SHIELD
+5V
XW884
XCL8010/Excel 500/600 cable details
EN1B-0375GE51 R0910
Planning
Features
5 m, shielded,
RJ45 plug with clip
See XW582 and
XW586
0.2 m, shielded,
RJ45 – 9 pin sub-D
3 m, shielded,
RJ45 plug with clip
See XW585 and
XW586
1.8 m, RJ45 – 9 pin
sub-D
LOOSE
XI582
ENDS
WIRING
TERMINALS
RS232 plug
sub-D female