Honeywell Excel 800 SYSTEM Installation And Commissioning Instructions page 68

Table of Contents

Advertisement

LON Software Interface Description
Default Service Type
The default service type of these variables is
unacknowledged.
Analog Sensor Output – nvoAiValuePct[ ]
If configured for voltage input, this network variable output
represents the percentage level for the appropriate input.
Valid Ranges for 0 ... 10 V Input
Value
< 0 V
0 V ... 10 V
> 10 V
Table 64 Analog input values: 0 ... 10 V
Valid Ranges for 2 ... 10 V Input
Value
< 1.5 V
1.5 V ... 2 V
2 V ... 10 V
> 10 V
Table 65 Analog input values: 2 ... 10 V
Default Value
The default value is set after power-up or reset and remains
until the module has measured a valid value.
nvoAiValuePct = INVALID = 0x7FFF (=163.835%)
The sensor failure behavior can be configured for 2 ... 10 V.
EN1B-0375GE51 R0910
Representation
0%
0 ... 100%
100%
Representation
Sensor break/short circuit
0%
0 ... 100%
100%
Temperature Sensor Output – nvoAiTempP[ ]
If configured for temperature sensor input (but not from
PT1000-2 temperature sensors), this network variable
output represents the temperature for the appropriate input.
Range: see Table 44 and Table 45 on page 40.
Default Value
The default value is set after power-up or reset and remains
until the module has measured a valid value.
nvoAiTempP = INVALID = 0x7FFF (= 327.67 °C)
Slow Digital Input – nvoAiSwitch[ ]
This network variable output represents a slow digital input
connected to the universal input terminals.
Valid Range
Sensor
Enabled
Disabled
Not configured
Table 66 Slow digital input values
Temperature#2 Sensor Output – nvoAiTemp[ ]
If configured for temperature sensor input (from PT1000-2
temperature sensors, only), this network variable output
represents the temperature for the appropriate input.
Range: see Table 44 and Table 45 on page 40.
Default Value
The default value is set after power-up or reset and remains
until the module has measured a valid value.
nvoAiTemp = INVALID = 0xFFFF (= 6279.5 °C)
68
Value
State
100%
1
0%
0
0%
-1
Excel 800

Advertisement

Table of Contents
loading

This manual is also suitable for:

Excel 5000 open system

Table of Contents