Description of the I/O Modules
Terminals
COM
71
A
COM
72
B
24
73
V~
24
74
V~0
BINARY
ANALOG
INPUTS
INPUTS
B7
B8 B9
AI5 AI6 AI7 AI8
B10 B11 B12
7
8 9 10 11 12
17 18 19 20
B1
B2
B3
B4
B5
B6
AI1 AI2
AI2 AI3 AI4
3
5
6
13 14
14 15 16
1
2
4
Fig. 88
Terminal assignment and internal connections of mixed Panel Bus I/O module terminals
Terminal
Signal
LED
71, 75
COM a
status
72, 76
COM b
status
73, 77
24 V~
power
74, 78
24 V~0
power
1...7
BI1...7
1...7
8...12
BI8...12
24...28
13...20
AI1...8
41, 42
GND
21...28
AO1...AO8
29...34
NO1...6
29...34
35...39
IN1...5
40
IN6
Table 61 Description of mixed Panel Bus I/O module
terminals
EN1B-0375GE51 R0910
ANALOG
GND
OUTPUTS
AO5 AO6 AO7
AO8
G1
G2
25 26 27
28
41
42
AO1 AO2 AO3 AO4
21 22 23 24
Comment
2-wire communication bus
(Panel Bus)
2-wire communication bus
(Panel Bus)
Power supply
Power supply
Binary inputs 1...7
Binary inputs 8...12
--
Analog inputs 1...8
Ground. Both grounds are
--
internally connected to each
other and to 24 VAC0.
--
Analog outputs 1...8
Relays 1...6, normally-open
contacts
Common contacts of relays
1...5. May be set to common
supply voltage via terminal 40
by inserting jumpers J1...J5 into
their lower positions. When, in
--
contrast, a jumper is in the
upper position (the so-called
"parking position" = default
setting), the corresponding relay
receives no supply voltage from
terminal 40.
Common contact of relay 6,
internally connected to the
--
middle contact of jumpers
J1...J5. May be used to connect
common supply voltage.
24 V RELAYS
J1
J2
JUMPER
JUMPER
JUMPER
IN1
IN2
IN3
35
R1
36
R2
37
R3
29
30
31
NO1
NO2
NO3
62
J3
J4
J5
JUMPER
JUMPER
IN4
IN5
IN6
38
R4
39
R5
R6
40
32
33
34
NO4
NO5
NO6
Excel 800
COM
75
A
COM
76
B
24
77
V~
24
78
V~0
EXT. 24VAC FOR
RELAY COMMON