Honeywell Excel 800 SYSTEM Installation And Commissioning Instructions page 45

Table of Contents

Advertisement

Excel 800
Technical Data
Voltage rating
Current rating
Resolution
Accuracy
Zero output voltage
Protection
Feedback signal
Table 48 Analog output modules data
Status LED Behavior
Automatic mode
Override mode
Table 49 Analog output status LED behavior
Status LEDs with Manual Overrides
1
2
4
3
Fig. 68.
Manual overrides (rotary knobs)
The XFR822/XFLR822 Analog Output Modules are
equipped with manual overrides: one for each analog
output. These rotary knobs can be manually set to either
"AUTO" or "0...100%" (infinitely adjustable).
NOTICE
Damage to the electronic module!
Do not use a tool to adjust the rotary knobs.
Do not use excessive force. Adjust only by hand.
Manual Override in the AUTO Position
When a manual override of the XFR822/XFLR822 is set to
AUTO, and the corresponding analog output has been
configured, the following applies:
0(2)...11 V (default)
max. ±1 mA
8 bit
±150 mV
< 200 mV
Short-circuit protected;
protected against failure
voltage (24 VAC, 40 VDC)
automatic/manual mode and
output value
Brightness is proportional to the
commanded output signal
Flashes
5
6
7
8
Honeywell
0
AUTO
!
If the L
W
ON
output voltage of the analog output will be as
commanded.
If the L
W
ON
output voltage of the analog output will be the safety
position value.
The brightness of the status LED (red) of the analog
output will be proportional to the commanded output
signal.
When a manual override of the XFR822/XFLR822 is set to
AUTO, and the corresponding analog output has not been
configured, the following applies:
Regardless as to whether the L
functioning properly or not, the output voltage of the
analog output will be 0 V (values from the L
Bus will be ignored, and there will be no heartbeat or
safety position).
The feedback signal on the L
nvoAoActPosnFb[ ] will have a value of 0% and a state
of 0.
The analog output status LED will be unlit.
Manual Override in the Override Position (0...100%)
When a manual override of the XFR822/XFLR822 is set to
0...100%, and the corresponding analog output has been
configured, the following applies:
The output voltage of the analog output will be 0...10 V
(direct) or 10...0 V (reverse).
The feedback signal on the L
nvoAoActPosnFb[ ] will have a value of 0...100% and a
state of -1.
The status LED (red) of the analog output will flash to
indicate "manual override."
When a manual override of the XFR822/XFLR822 is set to
100
0...100%, and the corresponding analog output has not
been configured, the following applies:
The output voltage of the analog output will be 0...10 V.
The feedback signal on the L
nvoAoActPosnFb[ ] will have a value of 0...100% and a
state of -1.
The status LED (red) of the analog output will flash to
indicate "manual override."
Note
Panel Bus I/O modules feature watchdog functionality. Con-
sequently, if the module's firmware stops running (due, e.g.,
to updating), the watchdog will switch OFF the module's
outputs – even if the corresponding manual overrides (if
present) have been set to ON. Thus, the manual overrides
should NOT be thought of as emergency overrides; rather,
they are subordinate to the given Panel Bus I/O module's
processor and firmware.
Analog Outputs Configured as Binary Outputs
Using CARE, the analog outputs can be configured
individually as binary outputs. The voltage output is then 0 V
or 10 V, depending upon the signal from the controller.
45
Description of the I/O Modules
network is functioning properly, the
ORKS
network is not functioning properly, the
ORKS
W
ON
ORKS
W
ON
ORKS
W
ON
ORKS
W
ON
ORKS
EN1B-0375GE51 R0910
network is
W
ON
ORKS
network
network
network