Interfaces And Bus Connections; Technical Data - Honeywell Excel 800 SYSTEM Installation And Commissioning Instructions

Table of Contents

Advertisement

System Overview

Interfaces and Bus Connections

The Excel 800 System can be connected to the following
devices and systems:
Panel Bus
 For communication with up to 16 Panel Bus I/O modules
 Polarity-insensitive
L
W
Bus
ON
ORKS
 For communication with other L
within the building
 FTT10, link power compatible
 Polarity-insensitive
C-Bus
 For communication with other controllers, e.g., existing
Excel 500 Controllers
HMI
 For connecting an operator interface, e.g., XI582,
XI882A, or a laptop, e.g., for CARE
Modem
 For connecting a modem or an ISDN terminal adapter

Technical Data

System Data
Operating voltage
Max. number of C-Bus
participants
Power consumption
Push-in terminals
Screw-type terminals
Overvoltage protection All inputs and outputs are
Calculated lifetime of
weakest component
under typical operating
conditions
Table 7 System data
EN1B-0375GE51 R0910
W
Bus devices
ON
ORKS
24 VAC, ± 20%, 21 ... 30 VDC
30
Max. 3.57 A
(1 XCL8010 Controller
+ 16 I/O modules)
2
1.5 mm
2
1.5 mm
protected against 24 VAC and
40 VDC overvoltage as well as
against short-circuiting.
MTBF
13.7 years
Standards
Protection class
Product standard EMC EN 60730-2-9
Testing electrical
components
Certification
System transformer
Low-Voltage Device
Safety Assessment
Table 8 Standards
Operational Environment
Ambient operating
temperature
Ambient operating
humidity
Ambient storage
temperature
Ambient storage
humidity
Vibration under
operation
Dust, vibration
RFI, EMI
Table 9 Operational environment
8
Excel 800
IP20
IEC68
CE
The system transformer(s) must
be safety isolating transformers
according to IEC 61558-2-6.
In the U.S.A. and Canada, NEC
Class 2 transformers must be
used.
EN 60730-1
EN 60730-2-9
0 ... 50 °C (32 ... 122 °F)
5 ... 93% relative humidity
(non-condensing)
–20 ... 70 °C (–4 ... +158 °F)
5 ... 95% relative humidity
(non-condensing)
0.024" double amplitude
(2 ... 30 Hz),
0.6 g (30 ... 300 Hz)
According to EN60730-1
Home environment

Advertisement

Table of Contents
loading

This manual is also suitable for:

Excel 5000 open system

Table of Contents