2.6.3 Power and sensor connection (±15 VDC sensors) with optional SPS module
[650 . . - . . A . - . . . . / 650 . . - . . C . - . . . . versions only]
Pins 4 and 8 must be bridged for operation!
An optional switch would allow for motor interlock
to prevent valve from moving.
Low range sensor may be connected to
sensor 1 or sensor 2 input.
Do configuration accordingly.
Note:
Use shielded sensor cable(s). Keep cable as short as possible, but locate it away from noise sources.
Connect the ±15 VDC sensors at DB–15 female sensor connector exactly as shown in the drawing above. Do not
connect other pins that may damage sensors, power supply or controller!
Connector: Use only screws with 4-40UNC thread for fastening the connectors!
Fehler! AutoText-Eintrag nicht definiert.
Installation, Operating & Maintenance Instructions
Series 650 DN 200 (I.D. 8"), DeviceNet
288667EB
13/74