Parameter name
MINIMUM SETPOINT
MAXIMUM SETPOINT
VALVE PROTECTION
MINIMUM TURN-OFF TIME
OPTIMISATION FEATURE
COMFORT WARM FLOOR
Parameter Values
MIN SETPOINT FOR HEATING
MIN SETPOINT FOR COOLING
MAX SETPOINT FOR HEATING
MAX SETPOINT FOR COOLING
ON
OFF
MIN OFF TIME FOR HEATING
MIN OFF TIME FOR COOLING
OPTIMUM START ON / OFF
OPTIMUM STOP ON / OFF
DISABLE
LEVEL 1
LEVEL 2
LEVEL 3
Description
When S1/S2 contacts are opened, thermostat activates standby
mode
ONE TOUCH - this option is available only in ONLINE mode. In
this scenario S1/S2 input is used to work with volt-free contact.
By closing/opening S1/S2 contacts we can trigger any OneTouch
rule created in the Smart Home application. More information
in chapter 6.15
CHANGEOVER - an external volt-free contact is connected to
the S1/S2 input.
When S1/S2 contacts are closed, thermostat works in heating
mode.
When S1/S2 contacts are opened, thermostat works in cooling
mode.
This function is not available when thermostat is paired with
KL08RF wiring centre, TRV head or RX10RF receiver.
This parameter allows to limit temperature setpoint range by
setting minimum setpoint for heating and cooling modes.
Default temperature setting range: 5⁰C - 35⁰C
This parameter allows to limit temperature setpoint range by
setting maximum setpoint for heating and cooling modes.
Default temperature setting range: 5,5⁰C - 40⁰C
Valve protection function is intended to protect thermostatic
valves against getting stuck or jamming (e.g. in summer time
when heating system is disabled). If thermostat doesn't send a
signal for heating for a period of 7 days, then heating is turned
on for a very short period of time just to move the actuators.
This parameter specifies the minimum time between ON/OFF
switching in cooling mode. Thermostat have to wait this time
value before it switches on again.
Minimum Turn-Off time range: 0 - 999
Optimisation function is an energy-saving algorithm for effec-
tive control of the heating device ensuring better temperature
comfort at pre-defined times of the day.
When the OPTIMUM START function is active, thermostats
sends the heating signal to the heat source earlier so that the
setpoint temperature is reached at the time defined in the
schedule.
When the OPTIMUM STOP function is active, thermostat takes
into account the system inertia, switches off the heat source
earlier to reach setpoint temperature at the time defined in the
schedule.
This function helps to keep the floor warm, even if the room is
warm enough and there is no need to turn on the heating. User
can select 3 levels of warm floor feature.
PLEASE NOTE: it is not an economy feature, as your heating
system may be ON even if there is no heating demand from the
room thermostat. It is COMFORT feature which keeps your floor
warm all the time. It is only for Heating Mode.
Default
Values
5 ⁰C
35 ⁰C
ON
FOR
HEATING: 1
FOR
COOLING:
180
OPTIMUM
START: OFF
OPTIMUM
STOP: OFF
DISABLE
63