Ul Listing Information; Common Ul Information; Power Dependant Ul Information; Ac Supply Specification - Johnson Controls VFD67 Series Getting Started Manual

Ac variable frequency drive for 3 phase induction motors
Hide thumbs Also See for VFD67 Series:
Table of Contents

Advertisement

Safety
Product
Mechanical
Information
Information
Installation
10

UL Listing Information

The Johnson Controls Inc UL file number is E244421. Confirmation of
UL listing can be found on the UL website: www.ul.com.
10.1

Common UL information

Conformity
The drive conforms to UL listing requirements only when the following
are observed:
The drive is installed in a type 1 enclosure, or better, as defined by
UL50
The ambient temperature does not exceed 40°C (104°F) when the
drive is operating
The terminal tightening torques specified in section 3.5.1 Terminal
sizes and torque settings on page 17.
Motor overload protection
The drive provides motor overload protection. The default overload
protection level is no higher than 150% of full-load current (FLC) of the
drive. It is necessary for the motor rated current to be entered into Pr 06
(or Pr 5.07) for the protection to operate correctly. The protection level
may be adjusted below 150% if required. The drive also provides motor
thermal protection.
Overspeed protection
The drive provides overspeed protection. However, it does not provide
the level of protection afforded by an independent high integrity
overspeed protection device.
10.2

Power dependant UL information

Conformity
The drive conforms to UL listing requirements only when the following is
observed:
Fuses
Size E to F
The correct UL-listed high speed/fast acting fuses (class CC up to
30A and class J above 30A), e.g. Bussman Limitron KTK series,
Gould Amp-Trap ATM series or equivalent, are used in the AC
supply. The drive does not comply with UL if MCBs are used in place
of fuses.
For further details on fusing, refer to section 2.2 Rating Data on page 7.
Field wiring
Size E to F
Class 1 60/75°C (140/167°F) copper wire only is used in the
installation
10.3

AC supply specification

The VFD67 is suitable for use in a circuit capable of delivering not more
than 100,000rms symmetrical Amperes at 264Vac rms maximum (200V
drives), 528Vac rms maximum (400V drives) or 600Vac rms maximum
(575V and 690V drives).
10.4

Maximum continuous output current

The drive models are listed as having the maximum continuous output
currents (FLC) shown in Table 10-1, Table 10-2, Table 10-3.
Table 10-1 Maximum continuous output current (200V drives)
Model
VFD67BKE
VFD67BME
VFD67BNF
VFD67BPF
Table 10-2 Maximum continuous output current (400V drives)
Model
VFD67CNE
VFD67CPE
VFD67 Size E to F Getting Started Guide
Issue Number: 1
Electrical
Keypad and
Parameters
Installation
Display
FLC (A)
22
28
42
54
FLC (A)
21
29
www.johnsoncontrols.com
Quick Start
Diagnostics
Commissioning
Table 10-3 Maximum continuous output current (575V drives)
Model
FLC (A)
VFD67DJF
5.4
VFD67DKF
8.4
VFD67DMF
11
10.5

Safety label

The safety label supplied with the connectors and mounting brackets
must be placed on a fixed part inside the drive enclosure where it can be
seen clearly by maintenance personnel for UL compliance.
The label clearly states "CAUTION Risk of Electric Shock Power down
unit 10 minutes before removing cover".
UL Listing
Technical
Parameter List
Information
specifications
Model
FLC (A)
VFD67DNF
16
VFD67DPF
22
43