Specifications; 4200Fa 15 / 25 Kva @ 208 Vac Input/ 208 Vac Output W/Internal Batteries - Toshiba 4200FA CT/XT User Manual

Toshiba 4200fa ct/xt uninterruptible power system three-phase 15/25/30/50 kva ups user's manual
Table of Contents

Advertisement

5.0 Specifications

5.1

4200FA 15 / 25 kVA @ 208 VAC Input/ 208 VAC Output w/Internal Batteries

Model Number
Rated Output Capacity
External Dimensions
W x D x H (cm)
Input
Rated Voltage
Voltage Variation
Rated Frequency
Input Cables required
Dual Input Option Cables required
* Power Factor
Required Input kVA
Walk-in Function
Inrush Current
Current Limit
* Harmonic Currents
Battery
DC Nominal (Voltage Range)
Float Charge (Regulation)
Ripple Voltage
**Rated Back-up Time
Rated Charge Current
Output
Rated Voltage
Rated Current
Rated Power Factor
Output Cables Required
Voltage Regulation (phase-phase)
Voltage Adjustment Range
Phase Displacement
Rated Frequency
Frequency Regulation
Frequency Synchronous
Frequency Slew Rate
Voltage Transients
(Recovery time: 50 ms)
Inverter Overload Capacity
Bypass Overload Capacity
Crest Factor
Neutral Line Conductor
Harmonic Voltage Distortion
Inrush Current protection
Environment
Efficiency (Typical)
Heat loss to be removed
Audible Noise
Operating Temperature
Operating Humidity
Altitude ***
Items marked with an (*) are specified at rated conditions under balanced linear loads.
(**) Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site, and an initial
charge time of 24 hrs is necessary to obtain proper battery performance level before the unit is placed in operation.
(***) At 6600-ft (2000 m) above sea level, output capacity should be derated by 3% (Consult Factory for higher elevations).
4200FA CT/XT User's Manual
TOSHIBA
C42F3F150XAMBN
C42F3F150##MBN
15 kVA
(50.8 cm x 92.2 cm x 151.6 cm)
+10% to -30%; (-15% to -30%)
3 phase ; 4 Wire + GND
3 phase ; 4 Wire + GND
Greater than 0.98 when in inverter mode
15 kVA
From 20% to 100% over 5 seconds
Less than 8 times the rated current under synchronous operation
Less than 8.5%
288 VDC (216 to 332 VDC)
7 min at full load
42.0 Amps
3 phase ; 4 Wire + GND
± 2% (0-100% balanced load); ± 3% (0-100% unbalanced load)
± 5V Manually from the key pad
± 2° (0–100% balanced load); ± 4° (unbalanced load)
± 0.1% in free running mode
± 0.5/1.0/1.5 Hz (± 1.0 Hz. std.)
switch selectable by qualified technician
1 Hz/s to 3Hz/s (in 0.5 Hz steps)
± 5% (100% load step change);
± 3% (loss or return of input voltage);
± 8% (transfer of bypass to inverter)
125% 90 sec; 150% 30 sec
1000% 10 ms; 125% 10 min.
2.5–3.0 within the kW range
1.73 (200%) times line rating
Automatic Transfer to bypass, then retransfer to inverter
AC/DC/AC: 82%; DC/AC: 86%
8,428 BTU/hr (2,124 kcal/hr)
60dB (A) at 1 meter from the front of the unit
32 –104 °F (0 – 40 °C); optimal temperature is 77 °F (25 °C)
30–90% RH (non condensing)
C42F3F250XAMBN
C42F3F250##MBN
25 kVA
20.0" x 36.3" x 59.7"
208 VAC
50 / 60 Hz
24 kVA
115% maximum
Less than 5.5%
324.0 VDC (± 2%)
0.5 V R.M.S.
5 min at full load
4.0 Amps
208 / 120 VAC
69.5 Amps
0.8 lagging
50 / 60 Hz
1.5% max (linear load)
AC/DC/AC: 85%; DC/AC: 87%
11,489 BTU/hr (2,895 kcal/hr)
Less than 2000 meters
31