Rs-232C; Ups Shutdown (Via Rs-232C) - Toshiba 4200FA CT/XT User Manual

Toshiba 4200fa ct/xt uninterruptible power system three-phase 15/25/30/50 kva ups user's manual
Table of Contents

Advertisement

4.5.2

RS-232C

The RS-232C serial communication interface is available through a DB9 female connector located
on the inside of the UPS. This interface allows control of the UPS from a computer network
running TOSHIBA RemotEyeII™ software. The computer and the UPS
serial RS-232C communication port. The available data from the UPS, via the RS-232C
communication link, is shown below:
Operating Conditions
UPS Operating Status
(Described as "yes or "no")
Fault Details
(Described as "occurred" or "not occurred")
The connector pin assignment and female connector outline are illustrated below.
Pin
I/O
Symbol
1
This pin is not used
2
Input
RXD
3
Output
TXD
4
Output
DTR
5
-
6
Input
DSR
7
Output
RTS
8
Input
CTS
9
This pin is not used
4.5.3

UPS Shutdown (via RS-232C)

When the UPS is operating from its internal batteries, a 'shutdown' order can be sent to the
UPS instructing it to turn OFF after a user-specified amount of time. This function can
allow you to stop discharging the UPS batteries after an orderly system shutdown has
been completed. The UPS can be programmed to turn OFF up to 8 minutes after the
'shutdown' command is given. This command can be cancelled before the specified time
has elapsed by following the directions listed on the RS-232C screen.
4200FA CT/XT User's Manual
TOSHIBA
Description
Receive Data
Transmit Data
Data Terminal Ready
SG
Signal Ground
Data Set Ready
Request To Send
Clear To Send
Input Voltage
Input Frequency
Battery Voltage
Utility Power OK
Low Battery Voltage Detected
UPS in BYPASS Mode
UPS in NORMAL Mode
Input and Output Frequency Synchronized
UPS FAULT Occurred
DC Bus Over-Current
DC Bus Over-Voltage
DC Bus Under-Voltage
Input Over-Current
Overheat
Overload Being Timed
Overload (allowable time exceeded)
Output Over-Voltage (during Normal Mode)
Output Under-Voltage (during Normal Mode)
DB9 Female connector outline
(facing connector)
5
4
3
9
8
are connected through a
Output Voltage
Output Frequency
Output Current
2
1
7
6
30