Recommended Wire Size And Torque Requirements - Toshiba 4200FA CT/XT User Manual

Toshiba 4200fa ct/xt uninterruptible power system three-phase 15/25/30/50 kva ups user's manual
Table of Contents

Advertisement

4.1.3

Recommended Wire Size and Torque Requirements

UPS Input and Output Terminals
Minimum Wire Size and Torque Requirements
UPS Input and Output Terminals 15/25/30 kVA
(USE MINIMUM 75 °C INSULATED COPPER WIRING)
Phase: (A) (B) (C)
Input: (H1) (H2) (H3)
208 V
220 V
240 V
380 V
400 V
415 V
480 V
600 V
All wire sizes are per the NEC. Maximum Wire Size is 2 AWG.
AWG
Output:
(L1)-
(L1) (L2) (L3) (N)
(L3)
120/208 V
8
127/220 V
8
240 V
8
220/380 V
10
230/400 V
10
240/415 V
10
277/480 V
10
600 V
10
Neutral Conductors are rated @ 1.73 or 200% of phase conductors, per NEC. Maximum Wire Size is 2
AWG.
Input/ Output (GND)
(G)
Maximum Wire Size is 2 AWG.
UPS Optional Separate Bypass Input "TB4" 15 / 25kVA
(USE MINIMUM 75 °C INSULATED COPPER WIRING)
Phase: (A) (B) (C)
Input: (H1) (H2) (H3)
208 V
220 V
240 V
380 V
400 V
415 V
480 V
600 V
Maximum Wire Size is 2 AWG.
4200FA CT/XT User's Manual
TOSHIBA
15 kVA
AWG
Torque
AWG
8
51 in-lbs.
4
8
51 in-lbs.
4
8
51 in-lbs.
4
10
35 in-lbs.
8
10
35 in-lbs.
8
10
35 in-lbs.
8
10
35 in-lbs.
8
10
35 in-lbs.
10
15 kVA
Torque
AWG
(inch-lbs.)
(N)
(L1)-(L3)
(N)
4
51
51
4
51
51
N/A
51
N/A
8
35
51
8
35
51
8
35
51
8
35
51
N/A
35
N/A
15 kVA
AWG
Torque
AWG
10
35 in-lbs.
8
Minimum Wire Size and Torque Requirements
15 kVA
AWG
Torque
8
51 in-lbs.
8
51 in-lbs.
8
51 in-lbs.
10
35 in-lbs.
10
35 in-lbs.
10
35 in-lbs.
10
35 in-lbs.
10
35 in-lbs.
25 kVA
30 kVA
Torque
AWG
51 in-lbs.
2
51 in-lbs.
2
51 in-lbs.
2
51 in-lbs.
6
51 in-lbs.
6
51 in-lbs.
6
51 in-lbs.
6
35 in-lbs.
10
25 kVA
AWG
Torque
AWG
(L1)-
(inch-lbs.)
(N)
(L3)
(L1)-(L3) (N)
4
2
51
4
2
51
4
N/A
51
8
4
51
8
4
51
8
4
51
8
6
51
10
N/A
35
25 kVA
30 kVA
Torque
AWG
51 in-lbs.
6
25 kVA
AWG
Torque
AWG
4
51 in-lbs.
2
4
51 in-lbs.
2
4
51 in-lbs.
2
8
51 in-lbs.
6
8
51 in-lbs.
6
8
51 in-lbs.
6
8
51 in-lbs.
6
10
35 in-lbs.
10
Torque
87 in-lbs.
87 in-lbs.
87 in-lbs.
51 in-lbs.
51 in-lbs.
51 in-lbs.
51 in-lbs.
35 in-lbs.
30 kVA
AWG
AWG
(L1)-
(N)
(L3)
87
2
2
87
2
2
N/A
2
N/A
51
6
2
51
6
2
51
6
2
51
6
2
N/A
10
N/A
Torque
51 in-lbs.
30 kVA
Torque
87 in-lbs.
87 in-lbs.
87 in-lbs.
51 in-lbs.
51 in-lbs.
51 in-lbs.
51 in-lbs.
35 in-lbs.
Torque
(inch-lbs.)
(L1)-(L3) (N)
87
87
87
87
87
N/A
51
87
51
87
51
87
51
87
35
N/A
22