6.11.1 LED (Light Emitting Diode) System Status

The following chart shows the UPS system status that can be determined by decoding the
"on" and "off" condition of the LED lamps. It should be used in conjunction with the LCD
display and the audible alarms for total system monitoring.
LED
(UPS On-Line, no abnormal conditions)
Bypass Operation; UPS Fault
Battery Back-up; (Battery Voltage Low)
6.12

LCD (Liquid Crystal Display) Functions

The LCD screen is a 4-line by 20-character wide display. The LCD display contains
information about the operation of the UPS. It should be used in conjunction with the LED
display and the audible alarms for total system monitoring. The LCD displays certain
information only on specific lines of the display. The UPS operating mode and conditions
determines the information shown. These messages are shown in the following line
message charts.

6.12.1 Line-1 System Messages

Line-1 messages are based on the operating mode. The following chart shows all
allowable Line-1 messages, which occur while starting up and while in main monitor
(MONI) screen mode.
- BYPASS OPERATION -
- BATTERY DISCHARGE -
- OUTPUT SHUTDOWN -
- BATTERY BACKUP -
4200FA CT/XT User's Manual
TOSHIBA
ON/OFF STATUS
Normal UPS Operation
AC IN
ON
INV
ON
BYP
OFF
BATT
OFF
FAULT
OFF
AC IN
ON
INV
OFF
BYP
ON
BATT
OFF
FAULT
ON
AC IN
OFF
INV
ON
BYP
OFF
BATT
ON (Blinking)
FAULT
OFF
LINE-1 MESSAGES
Display Message
- UPS START UP -
- UPS ON-LINE -
LED
Output Shutdown
(After EPO received (Emergency Power Off ))
AC IN
INV
BYP
BATT
FAULT
Fatal Communication Error
(Display to Control Interface)
AC IN
INV
BYP
BATT
FAULT
Translation
Displayed when UPS is in the start-up condition
or display board is resetting.
Displayed when the UPS is in Bypass
Operation.
Displayed when the inverter is running, and no
abnormality exists.
Displayed during abnormal Utility occurrences;
inverter is supplying power from batteries. (UPS
shuts down after V (min.) is reached.
Displayed during power failure if V (min.) is
reached, an EPO is received, or after
completion of Shutdown Sequence of the
Inverter and Bypass is not available.
Displayed during input power failure.
ON/OFF STATUS
OFF
OFF
OFF
OFF
OFF
ALL ON OR FLICKERING
RAPIDLY
44