Configuring The Dip Switches; Dip Switch Settings - Banner SureCross DX80 Series Manual

Configurable node with 2 discrete inputs, 2 discrete outputs, 2 analog inputs, and 2 analog outputs
Hide thumbs Also See for SureCross DX80 Series:
Table of Contents

Advertisement

7. Install your wireless sensor network components. If installation instructions are not included in this datasheet, refer to the product
manual for detailed installation instructions.
For additional information, including installation and setup, weatherproofing, device menu maps, troubleshooting, and a list of accesso-
ries, refer to one of the following product manuals.
• SureCross Quick Start Guide: Banner part number
• SureCross Wireless I/O Network Manual:
• Web Configurator Manual (used with "Pro" and DX83 models):
• Host Configuration Manual

Configuring the DIP Switches

Before making any changes to the DIP switch positions, disconnect the power. DIP switch changes will not be recognized if power isn't
cycled to the device.
For parameters not set via DIP switches, use the User Configuration Tool (UCT) to make configuration changes. For parameters set
using the DIP switches, the DIP switch positions override any changes made using the User Configuration Tool.
Accessing the Internal DIP Switches
To access the internal DIP switches, follow these steps:
1. Unscrew the four screws that mount the cover to the bottom housing.
2. Remove the cover from the housing without damaging the ribbon cable or the pins the cable plugs into.
3. Gently unplug the ribbon cable from the board mounted into the bottom housing.
4. Remove the black cover plate from the bottom of the device's cover.
The DIP switches are located behind the rotary dials.
After making the necessary changes to the DIP switches, place the black cover plate back into position and
gently push into place. Plug the ribbon cable in after verifying that the blocked hole lines up with the missing
pin. Mount the cover back onto the housing.

DIP Switch Settings

Device Settings
Rotary dial address mode
Extended address mode
Modbus or UCT configured (overrides DIP switches
3-8)
DIP switch configured
Inputs sourcing (PNP)
Inputs sinking (NPN)
Link loss output: zero
Link loss output: one
Link loss output: hold last state
Link loss output: user configuration
0–20 mA scale (Not used in 0-10V analog models)
4–20 mA scale (Not used in 0-10V analog models)
* Default configuration
2
128185
132607
132114
1
OFF*
ON
www.bannerengineering.com - tel: 763-544-3164
134421
Switches
2
3
4
OFF*
ON
OFF*
ON
OFF*
OFF
ON
ON
SureCross DX80 Node
5
6
7
OFF*
ON
OFF
ON
OFF*
ON
P/N 131295 Rev. F
8