Dip Switch Settings - Banner SureCross DX80G9M6S0P0V4V4C Manual

Table of Contents

Advertisement

SureCross DX80 Gateway
1. Unscrew the four screws that mount the cover to the bottom housing.
2. Remove the cover from the housing without damaging the ribbon cable or the pins the cable plugs into.
3. Gently unplug the ribbon cable from the board mounted into the bottom housing.
4. Remove the black cover plate from the bottom of the device's cover.
The DIP switches are located behind the rotary dials.
After making the necessary changes to the DIP switches, place the black cover plate back into position and
gently push into place. Plug the ribbon cable in after verifying that the blocked hole lines up with the missing
pin. Mount the cover back onto the housing.

DIP Switch Settings

Device Settings
Rotary switch address mode
Extended address mode
Modbus or UCT configured (overrides DIP
switches 3-8)
DIP switch configured
Link loss output: zero
Link loss output: one
Link loss output: hold last state
Link loss output: user configuration
0–20 mA scale (Not used on 0–10V I/O models.)
4–20 mA scale (Not used on 0–10V I/O models.)
* Default configuration
Address Mode
The SureCross wireless devices may use one of two types of addressing modes: rotary dial addressing or extended addressing. In
rotary dial address mode, the left rotary dial establishes the network ID and the right rotary dial sets the device ID. The wireless network
is restricted to a maximum of 16 devices.
Extended address mode uses a security code to "bind" Nodes to a specific Gateway. Bound Nodes can only send and receive informa-
tion from the Gateway to which they are bound. In extended address mode, wireless networks may contain up to 48 radio devices. For
more information on extended address mode, refer to the SureCross™ Wireless I/O Network product manual.
The device ships in rotary dial address mode by default, with the DIP switch in the OFF position. To use extended address mode, change
the DIP switch to the ON position.
Link Loss Outputs
The SureCross DX80 wireless devices use a deterministic radio link time-out method to address RF link interruption or failure. When a
radio link fails, all pertinent wired outputs are sent to defined states until the link is recovered, ensuring that disruptions in the communica-
tions link result in predictable system behavior.
Following a radio link time-out, all outputs linked to the Node in question are set to de-energize (discrete outputs to zero, analog outputs
to 0 mA or 4 mA), energize (discrete outputs to one, analog outputs to 20 mA), or to hold the last stable state/value. Use the DIP switches
to select the link loss output state.
Modbus/User Configuration Tool (UCT) or DIP Switch Configured
In Modbus/UCT Configured mode, the device parameters are changed using the User Configuration Tool (UCT) or a Modbus command.
All DIP switch positions are ignored. In DIP Switch Configured mode, use the DIP switches to configure the parameters listed in the table.
P/N 136325 Rev. F
1
2
3
OFF*
ON
OFF*
ON
www.bannerengineering.com - tel: 763-544-3164
Switches
4
5
6
OFF*
OFF*
OFF
ON
ON
OFF
ON
ON
OFF*
ON
7
8
3

Advertisement

Table of Contents
loading

Table of Contents